Trip snapshot, Trip snapshot group – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 94

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
95
Trip History and Snapshot Chapter 8
Trip Snapshot
The EC4 Current Monitoring Relay with firmware revision 5.01 and higher will
record up to four real time data parameters in non-volatile memory in the event
of an EC4 Current Monitoring Relay trip. This information can be used by
maintenance personnel to understand the electrical conditions of the electric
motor at the time of the trip.
Trip Snapshot Group
WarnHistory Mask
This parameter allows the user to configure
which current based protection features are
written to the five record Warning History
as outlined in the table below:
1 = Recorded
0 = Not Recorded
Parameter Number
143
Access Rule
Get/Set
Data Type
UINT
Object Mapping
0Fhex-8F-01
Group
TripWarn History
Units
—
Minimum Value
0000000000000000
Maximum Value
0111111111111111
Default Value
0111111111111111
Bit
Function:
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
X
Ground Fault
X
L1 Undercurrent
X
L2 Undercurrent
X
L3 Undercurrent
X
L1 Overcurrent
X
L2 Overcurrent
X
L3 Overcurrent
X
L1 Loss
X
L2 Loss
X
L3 Loss
X
Comm Fault
X
Comm Idle
X
Config Fault
X
PM Starts
X
PM Oper Hours
Reserved
SS L1 Current
This parameter reports the value of L1
Current at the time of the last relay trip.
Parameter Number
144
Access Rule
Get
Data Type
INT
Object Mapping
0Fhex-90-01
Group
Trip Snapshot
Units
Amps
Minimum Value
0
Maximum Value
32767
Default Value
—