Environmental specifications – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 119

120
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Appendix A Specifications
Environmental
Specifications
➊ Current ratings must be derated at altitudes greater than 2000 m
Off-State Current
0.5 mA
Transition Voltage
5...15V DC
Transition Current
0.5...2.0 mA
Table 5 - Thermistor/PTC Input Ratings
Terminals
1T1, 1T2
Type of Control Unit
Mark A
Maximum Number of Sensors
6
Maximum Cold Resistance of PTC Sensor Chain
1500
Ω
Trip Resistance
3400
Ω ± 150 Ω
Reset Resistance
1600
Ω ± 100 Ω
Short-circuit Trip Resistance
25
Ω ± 10 Ω
Maximum Voltage @ PTC Terminals (R
PTC
= 4
k
Ω)
7.5V DC
Maximum Voltage @ PTC Terminals (R
PTC
=open)
30V DC
Response Time
800 ms
Table 4 - Input Ratings
Table 6 - Environmental Specifications
Ambient Temperature
Storage
Operating
(Open)
(Enclosed)
–40
°…+85°C (–40…+185°F)
–20
°…+55°C (–4°…+131°F)
–20
°…+40°C (–4°…+104°F)
Humidity
Operating
Damp Heat – Steady State (per IEC 68-2-3)
Damp Heat – Cyclic (per IEC 68-2-30)
5…95% Non-condensing
92% r.h., 40
°C (104°F), 56 days
93% r.h., 25
°C/40°C (77°F/104°F), 21 Cycles
Cooling Method
Natural Convection
Vibration (per IEC 68-2-6)
3 G
Shock (per IEC 68-2-27)
30 G
Maximum Altitude
2000 m ➊
Pollution Environment
Pollution Degree 3
Terminal Marking
EN 50012
Degree of Protection
193-ECxxx
592-ECxxx
IP20