Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 67

68
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
➊
For Catalog Number 193-EC4ZZ
➊
For Catalog Number 193-EC4ZZ
L2 UC Trip Delay
This parameter allows the installer to
program a time duration for which an under
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
112
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-163
Group
Advanced Setup
Units
0.1 Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
L2 UC Warn Level
This parameter sets the under current
warning level for line 2.
Parameter Number
113
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-164
2C
hex
-1-119
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
L3 UC Trip Level
This parameter sets the under current trip
level for line 3.
Parameter Number
114
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-165
2C
hex
-1-186
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
L3 UC Trip Delay
This parameter allows the installer to
program a time duration for which an under
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
115
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-166
Group
Advanced Setup
Units
0.1 Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0