Devicenet setup group – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 72

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
73
Programmable Parameters Chapter 5
DeviceNet Setup Group
PROGRAM LOCK
This parameter prohibits the device
parameters from being altered when set to
“Locked”.
This parameter must be set to “Unlocked” to
allow parameter modification.
Parameter Number
53
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0xB4-1-18
Group
Reset/Lock
Units
—
Minimum Value
0 = Unlocked
Maximum Value
1 = Locked
Default Value
0
SET TO DEFAULTS
This parameter allows the user to reset the
parameter settings to the factory default
values. After parameter values have been
reset to the factory default settings, the
parameter automatically returns to a
“Ready” state.
Parameter Number
54
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0xB4-1-19
Group
Reset/Lock
Units
—
Minimum Value
0 = Ready
Maximum Value
1 = Set
Default Value
0
Test Enable
This parameter allows the installer to enable
or disable the test function of the Test/Reset
button.
Parameter Number
103
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
29hex-1-108
Group
Reset/Lock
Units
—
Minimum Value
0 = Disable
Maximum Value
1 = Enable
Default Value
1
Clear Queue
This parameter allows the user to clear the
Trip Logs, Warning Logs, Starts Counter, and
the Elapsed Time. Setting the Clear Queue
parameter to "1" will clear/reset the Trip
Logs, Warning Logs, Starts Counter, and the
Elapsed Time parameters at the same time.
Parameter Number
104
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
29hex-1-132
Group
Reset/Lock
Units
—
Minimum Value
0 = Ready
Maximum Value
1 = Clear
Default Value
0
AUTO BAUD ENABLE
When this parameter is enabled, the device
will attempt to determine the network baud
rate and set its baud rate to the same,
provided network traffic exists.
At least one node with an established baud
rate must exist on the network for autobaud
to occur.
Parameter Number
55
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0xB4-1-15
Group
DeviceNet Setup
Units
—
Minimum Value
0 = Disabled
Maximum Value
1 = Enabled
Default Value
1