Assembly object – class code 0x04, Output assemblies – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 125

126
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Appendix B DeviceNet Information
➊ Allocation byte
Bit 0
Explicit Messaging
Bit 1
Polled I/O
Bit 4
Change of State I/O
Bit 5
Cyclic I/O
Bit 6
Acknowledge Suppress I/O
The following services are implemented for the DeviceNet Object:
Assembly Object – Class
Code 0x04
Output Assemblies
The following Assembly Instances are implemented. Note that most of these
assemblies are part of the “motor control hierarchy” of the DeviceNet
specification. Other vendor specific assemblies have been added to allow the
monitoring of the auxiliary inputs, etc.
The following assemblies are similar to those found in the Motor Starter Profile.
The only difference is that OutA and OutB map to Discrete Output Points
instead of the Control Supervisor. The instance numbers are 100 plus the
number assigned in corresponding assemblies in the Motor Starter Profile.
Table 17 - DeviceNet Object Instance Attributes
Attribute
ID
Access
Rule
Name
Data Type
Value
1
Get/Set
MAC ID
USINT
0...63
2
Get/Set
Baud Rate
USINT
0 = 125 kbaud
1 = 250 kbaud
2 = 500 kbaud
5
Get
Allocation Information
Allocation’s Choice Byte
Master’s MAC ID
Structure
of:
BYTE
USINT
Allocation byte ➊
0...63 = address
255 = unallocated
Table 18 - DeviceNet Object Common Services
Service
Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x4B
No
Yes
Allocate_Master/Slave_Connection_Set
0x4C
No
Yes
Release_Master/Slave_Connection_Set
Table 19 - Assembly Object Instance 2 Data Format (“TRIP RESET CMD”)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit3
Bit 2
Bit 1
Bit 0
0
Fault
Reset