beautypg.com

Using rsnetworx for devicenet – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 48

background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

49

DeviceNet Node Commissioning Chapter 4

Figure 24 - Node Address Switches

2.

For node address switch values in the range of 0 to 63, cycle power to the
EC4 Current Monitoring Relay to initialize the new setting.

Using RSNetWorx for DeviceNet

Going Online

Follow these additional steps for node address switch settings in the range of
64…99. To begin the configuration of an EC4 Current Monitoring Relay using
software, execute the RSNetWorx software and complete the following
procedure. You must use RSNetWorx Revision 3.21 Service Pack 2 or later.

1.

After going on-line using RSNetWorx for DeviceNet, do the following:
• Select the “Network” menu.
• Select “Online”.

2.

Choose the appropriate DeviceNet PC interface. In this example, a
1784-PCD module is chosen. Other common DeviceNet interfaces are the
1770-KFD and 1784-PCIDS.

Table 13 - Node Address Setting

Switch Settings

Description

0…63

The node address setting is determined by the switch values when
set in this range.

64…99

For switch settings in this range, the node address setting is
determined by the software setting using the RSNetWorx for
DeviceNet configuration tool.

99

Factory default setting.

IMPORTANT

Resetting an EC4 Current Monitoring Relay to factory default values will
also effect the node address setting for node address switch settings of
64 to 99.