Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 78

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
79
Programmable Parameters Chapter 5
OUTB PR FLTVALUE
This parameter determines the state that
Output B assumes when a trip occurs and
Parameter 71 is set to “0”.
Parameter Number
72
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-2-114
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Open
Maximum Value
1 = Closed
Default Value
0
OUTB DN FLTSTATE
This parameter, in conjunction with
Parameter 74, defines how Output B will
respond when a DeviceNet network fault
occurs. When set to “1”, Output B will hold
the state prior to trip occurrence. When set
to “0”, Output B will open or close as
determined by the setting in Parameter 74.
Output B can be configured to go to a desired
state in the event of a DeviceNet network
fault independent from enabling CommFault
in Parameter 24, Trip Enable.
Parameter Number
73
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-2-5
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Go to FltValue (#74)
Maximum Value
1 = Hold Last State
Default Value
0
OUTB DN FLTVALUE
This parameter determines the state that
Output B assumes when a comm fault occurs
and Parameter 73 is set to “0”.
Parameter Number
74
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-2-6
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Open
Maximum Value
1 = Closed
Default Value
0
OUTB DN IDLSTATE
This parameter, in conjunction with
Parameter 76, defines how Output B will
respond when the DeviceNet network is idle.
When set to “1”, Output B will hold the state
prior to trip occurrence. When set to “0”,
Output B will open or close as determined by
the setting in Parameter 76.
The Dn Flt parameters supersede the Dn Idl
parameters.
Parameter Number
75
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-2-7
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Go to IdlValue (#76)
Maximum Value
1 = Hold Last State
Default Value
0
OUTB DN IDLVALUE
This parameter determines the state that
Output B assumes when the network is idle
and Parameter 75 is set to “0”.
Parameter Number
76
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-2-8
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Open
Maximum Value
1 = Closed
Default Value
0