Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 70

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
71
Programmable Parameters Chapter 5
➊
For Catalog Number 193-EC4ZZ
➊
For Catalog Number 193-EC4ZZ
L3 OC Trip Level
This parameter sets the over current trip
level for line 3.
Parameter Number
124
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-175
2C
hex
-1-189
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
L3 OC Trip Delay
This parameter allows the installer to
program a time duration for which an over
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
125
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-176
Group
Advanced Setup
Units
0.1 Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
L3 OC Warn Level
This parameter sets the over current warning
level for line 3.
Parameter Number
126
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-177
2C
hex
-1-123
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
LL Inhibit Time
This parameter sets the time in which line
loss protection is inhibited during a starting
sequence.
Parameter Number
127
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-114
Group
Advanced Setup
Units
0.1 Seconds
Minimum Value
0.0
Maximum Value
25.0
Default Value
0.1