Acknowledge handler object – 0x2b – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 142

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
143
DeviceNet Information Appendix B
The following common services are implemented for the Control Supervisor
Object:
Acknowledge Handler
Object – 0x2B
The following class attributes are supported for the Acknowledge Handler
Object:
A single instance (instance 1) of the Acknowledge Handler Object is supported.
The following instance attributes are supported:
126
Get/Set
Trip Reset
BOOL
0->1 = Trip Reset
otherwise no action
130
Get/Set
Reset Mode
BOOL
0 = Manual
1 = Automatic
131
Get/Set
OL Reset Level
USINT
%FLA
132
Get/Set
Clear Queues
BOOL
0->1 = Clear fault and warning queues, start
counters and operating hour accumulators
otherwise no action
177
Get/Set
IN1 Assignment
USINT
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed
178
Get/Set
IN2 Assignment
USINT
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed
179
Get/Set
IN3 Assignment
USINT
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed
180
Get/Set
IN4 Assignment
USINT
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed
Table 59 - Control Supervisor Object Common Services
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x05
No
Yes
Reset
Table 58 - Control Supervisor Object Instance Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Value
Table 60 - Acknowledge Handler Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1