Typical control circuit wiring diagrams, Cat. no. 19 3 -cbct4 – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 32

background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

33

Installation and Wiring Chapter 2

Figure 19 - Cat. No. 193-CBCT2, -CBCT3 Approximate Dimensions [mm (in.)]

Figure 20 - Cat. No. 193-CBCT4 Approximate Dimensions [mm (in.)]

Typical Control Circuit
Wiring Diagrams

11.

8

(.47)

3

.2

(.1

3

)

Ø

D

5.

3

(.21)

E

F

B

A

C

96

(

3

.7

8

)

Cat. No.

19

3

-CBCT2

A

8

9.6

(

3

.5

3

)

B

4

8

.

3

(1.90)

C

Dimen

s

ion

s

3

9.6

(1.56)

ø D

54.6

(2.15)

E

69.9

(2.75)

122.4
(4.

8

2)

19

3

-CBCT

3

115.9
(4.56)

59.7

(2.

3

5)

6

3

.5

(2.50)

54.1

(2.1

3

)

96

(

3

.7

8

)

F

44.5

(1.75)

56.2

(2.21)

74.4

(2.9

3

)

12

3

.2

(4.

8

5)

96.7

(

3

.

8

1)

Cat. No. 19

3

-CBCT4

11.

8

(.47)

146.

8

(5.7

8

)

14

3

.5

(5.65)

5.5

(.22)

74.9

(2.95)

3

.2

(.1

3

)

8

2.6

(

3

.25)

ATTENTION: The ratings of the EC4 Current Monitoring Relay’s
output and trip relay must not be exceeded. If the coil current or
voltage of the contactor exceeds the relay’s ratings, an
interposing relay must be used.

ATTENTION: When the power is applied to the EC4 Current
Monitoring Relay (DeviceNet terminals V+ and V-), the N.O. trip
relay contact across terminals 95 and 96 will close after
approximately 2.35 seconds if no trip condition exists.