Rockwell Automation Publication 193-UM011A-EN-P - September 2010

119

Specifications Appendix A

Table 3 - Output and Trip Relay Ratings

Terminals

OUT A:
OUT B (E3 Plus):
Trip Relay:

13/14
23/24
95/96

Type of Contacts

Form A
SPST - NO

Rated Thermal Current (I

the

)

5 A

Rated Insulation Voltage (U

i

)

300V AC

Rated Operating Voltage (U

e

)

240V AC

Rated Operating Current (I

e

)

3 A (@120V AC), 1.5 A (@240V AC)

0.25 A (@110V DC), 0.1 A (@220V DC)

Minimum Operating Current

10 mA @ 5V DC

Rating Designation

B300

Utilization Category

AC-15

Resistive Load Rating (p.f. = 1.0)

5 A, 250V AC
5 A, 30V DC

Inductive Load Rating (p.f. = 0.4)
(L/R = 7 ms)

2 A, 250V AC
2 A, 30V DC

Short Circuit Current Rating

1,000 A

Recommended Control Circuit Fuse

KTK-R-6
(6 A, 600 V)

Rated Number of Operations

Trip Relay:
OUT A and B:
W/100-C09…100-C43
W/100-C60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3

100,000

5,000,000
2,500,000
1,000,000
300,000

Table 4 - Input Ratings

Terminals

IN 1:
IN 2:
IN 3 (E3 Plus):
IN 4 (E3 Plus):
Supply Voltage (24V DC):

1
2
3
4
5,6

Supply Voltage
(provided by E3)

24V DC ± 10%

Type of Inputs

Current Sinking

On-State Voltage

15V DC

On-State Current (turn-on)

2 mA

Steady State Current

8 mA

Off-State Voltage

5V DC