Chapter 2 Installation and Wiring
Control and DeviceNet Terminals
For reliable input signal processing, input wiring should be routed in raceways
separate from power cabling.
Terminal Designations
Control Terminals
The following table defines the EC4 Current Monitoring Relay control terminal
designations.
Table 3 - Control and DeviceNet Terminal Wire Size and Torque Specification
Cat. No.
All Types
Stranded/Solid
AWG
Single Conductor
Multiple Conductor
Torque
24...12 AWG
24...16 AWG
5 lb-in
Flexible-Stranded with Ferrule
Metric
Single Conductor
Multiple Conductor
Torque
0.25...2.5 mm
2
0.5...0.75 mm
2
0.55 Nm
Coarse-Stranded/Solid
Metric
Single Conductor
Multiple Conductor
Torque
0.2...4.0 mm
2
0.2...1.5 mm
2
0.55 Nm
Table 4 - Maximum Wire Lengths (Input)
Min. Cross
Section
mm
2
0.5
0.75
1.5
2.5
4.0
AWG
20
18
16
14
12
Max.
Length ➊
m
160
250
400
600
1000
ft
525
825
1300
1950
3200
Table 5 - Ground Fault Sensor Terminals (S1 and S2)
Wire type
Shielded, twisted pair
Cross section
0.2…4.0 mm
2
(#24…12 AWG)
Torque
0.55 N
•
m (5 lb-in.)
Table 6 - Control Terminal Designation
Terminal
Designation
Reference
Description
1
IN 1
General-purpose sinking input number 1
2
IN 2
General-purpose sinking input number 2
3
IN 3
General-purpose sinking input number 3
4
IN 4
General-purpose sinking input number 4
5
V+
+24V DC supply for inputs
6
V+
End
Earth Ground
➊
13/14
OUT A
Output A
23/24
OUT B
Output B