Logic supervisor object - class code 0x030e – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 145

146
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Appendix B DeviceNet Information
Logic Supervisor Object -
CLASS CODE 0x030E
A single instance (instance 1) will be supported. The following instance
attributes will be supported.
The following common services will be implemented for the Logic Supervisor
Object.
Status Object - CLASS
CODE 0x0375
The following instance attributes are for the EC4 Current Monitoring Relay:
28
Jam
112
L3Overcurrent
60
Hardware / Config Flt
62
Non-Volatile Memory
Table 65 - ODVA Fault Codes
Trip Code
Description
Trip Code
Description
Table 1: Logic Supervisor Object Instance Attributes
Attribute ID
Access
Rule
Name
Data Type
Range
Value
1
Get/Set
Logic Enable
BOOL
0=Logic
Disabled
1=Logic
Enabled
0
2
Get
Data Table
Array of
BYTE
The Standard
Bit Table
0
5
Get
Last Error
UDINT
Last error
code
65
6
Get
FB Classes
Implemented
STRUCT of:
USINT
Array of
UINT
4
775, 776,
777, 778
0x3F
Table 2: Logic Supervisor Object Common Services
Service
Code
Implemented for:
Service
Name
Class
Instance
0x08
No
Yes
Reset
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table 3: EC4 Status Object Instance Attributes
Attribute
Name
Byte
Data
1
Phase / Gnd Currents
0
L1 Current
1
2
L2 Current
3
4
L3 Current
5
6
Ground Current
7