Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 69

70
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
➊
For Catalog Number 193-EC4ZZ
➊
For Catalog Number 193-EC4ZZ
➊
For Catalog Number 193-EC4ZZ
L1 OC Warn Level
This parameter sets the over current warning
level for line 1.
Parameter Number
120
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-171
2C
hex
-1-121
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
L2 OC Trip Level
This parameter sets the over current trip
level for line 2.
Parameter Number
121
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-172
2C
hex
-1-188
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
L2 OC Trip Delay
This parameter allows the installer to
program a time duration for which an over
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
122
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-173
Group
Advanced Setup
Units
0.1 Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
L2 OC Warn Level
This parameter sets the over current warning
level for line 2.
Parameter Number
123
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-174
2C
hex
-1-122
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value