Appendix B DeviceNet Information
Multiple instances of the Discrete Output Point Object are supported, one
instance for each general purpose discrete output on the EC4 Current
Monitoring Relay. All instances will contain the following attributes:
The following common services are implemented for the Discrete Output Point
Object:
Parameter Object – Class
Code 0x0F
The following class attributes are supported for the Parameter Object:
Multiple instances of the Parameter Object are supported. All instances will
contain the following attributes:
Table 44 - Discrete Output Point Object Instance Attributes
Attribute ID
Access
Rule
Name
Data Type
Value
3
Get/Set
Value
BOOL
Output point value.
0 = OFF; 1 = ON
5
Get/Set
Fault Action
BOOL
0 = Go to fault value
1 = Hold last state
6
Get/Set
Fault Value
BOOL
0 = OFF
1 = ON
7
Get/Set
Idle Action
BOOL
0 = Go to Idle Action
1 = Hold Last State
8
Get/Set
Idle Value
BOOL
0 = OFF
1 = ON
113
Get/Set
Protection Fault Action
BOOL
0 = Go to Pr Fault Value
1 = Ignore
114
Get/Set
Protection Fault Value
BOOL
0 = OFF
1 = ON
Table 45 - Discrete Output Point Object Common Services
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table 46 - Parameter Object Class Attributes
Attribute
ID
Access
Rule
Name
Data Type
Value
1
Get
Revision
UINT
1
2
Get
Max Instances
UINT
Product Code
Dependent
8
Get
Parameter Class
Descriptor
WORD
0x03
10
Get
Native Language
USINT
1 = English