Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 127

128
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Appendix B DeviceNet Information
The following tables indicate the I/O Assembly Data Attribute mapping for
Parameter Link-Based Assemblies:
Table 28 - Assembly Object Instance 107 Data Format (“STATUS”)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit3
Bit 2
Bit 1
Bit 0
0
Input4
Input3
Input2
Input1
OutB_Stat
OutA_Stat
Warning Faulted
Table 29 - Assembly Object Instance 141 Data Format (“DEVICELOGIX STAT”)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit3
Bit 2
Bit 1
Bit 0
0
Input4
Input3
Input2
Input1
OutB_Stat
OutA_Stat
Warning Faulted
1
Network
Output 7
Network
Output 6
Network
Output 5
Network
Output 4
Network
Output 3
Network
Output 2
Network
Output 1
Network
Output 0
2
DeviceLog
ix Enabled
Network
Output
14
Network
Output 13
Network
Output 12
Network
Output 11
Network
Output 10
Network
Output 9
Network
Output 8
Table 30 - Assembly Object Instance 184 Data Format (“PNB STATUS”)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit3
Bit 2
Bit 1
Bit 0
0
Network
Output 7
Network
Output 6
Network
Output 5
Network
Output 4
Network
Output 3
Network
Output 2
Network
Output 1
Network
Output 0
1
DeviceLogi
x Enabled
Network
Output
14
Network
Output 13
Network
Output 12
Network
Output 11
Network
Output 10
Network
Output 9
Network
Output 8
Table 31 - Assembly Object Instance 100 Attributes (“PARAMETER BASED”)
Byte
Word
Value
0
0
Value of parameter pointed to by param #61 (Low Byte)
1
Value of parameter pointed to by param #61 (High Byte)
2
1
Value of parameter pointed to by param #62 (Low Byte)
3
Value of parameter pointed to by param #62 (High Byte)
4
2
Value of parameter pointed to by param #63 (Low Byte)
5
Value of parameter pointed to by param #63 (High Byte)
6
3
Value of parameter pointed to by param #64 (Low Byte)
7
Value of parameter pointed to by param #64 (High Byte)
Table 32 - Instance 110 Data Link Output Assembly Attributes
(“PARAM LINK CMD”)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit3
Bit 2
Bit 1
Bit 0
0
Remote
Trip
Fault
Reset
Output B Output A
1
Reserved