Programmable Parameters Chapter 5
IN3 ASSIGNMENT
This parameter allows the user to assign a
specific function to the discrete IN3 input.
Parameter Number
85
Access Rule
Get/Set
Data Type
USINT
Object Mapping
29
hex
-1-179
Group
Advanced Setup
Units
—
Minimum Value
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = L1 Loss Arm
4 = L2 Loss Arm
5 = L3 Loss Arm
6 = L1 L2 Loss Arm
7 = L2 L3 Loss Arm
8 = L1 L3 Loss Arm
Maximum Value
9 = L1 L2 L3 Loss Arm
Default Value
0
IN4 ASSIGNMENT
This parameter allows the user to assign a
specific function to the discrete IN4 input.
Parameter Number
86
Access Rule
Get/Set
Data Type
USINT
Object Mapping
29
hex
-1-180
Group
Advanced Setup
Units
--
Minimum Value
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = L1 Loss Arm
4 = L2 Loss Arm
5 = L3 Loss Arm
6 = L1 L2 Loss Arm
7 = L2 L3 Loss Arm
8 = L1 L3 Loss Arm
Maximum Value
9 = L1 L2 L3 Loss Arm
Default Value
0
GF TRIP INHIBIT
This parameter allows the installer to inhibit
a ground fault trip from occurring when the
ground fault current exceeds the maximum
range of the core balance sensor
(approximately 10 A).
Parameter Number
89
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
Group
Advanced Setup
Units
--
Minimum Value
0 = Disabled
Maximum Value
1 = Enabled
Default Value
0