Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 77

78
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
OUTA DN FLTSTATE
This parameter, in conjunction with
Parameter 68, defines how Output A will
respond when a DeviceNet network fault
occurs. When set to “1”, Output A will hold
the state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by the setting of Parameter 68.
Output A can be configured to go to a desired
state in the event of a DeviceNet network
fault independent from enabling CommFault
in Parameter 24, Trip Enable.
Parameter Number
67
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-1-5
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Go to FltValue (#68)
Maximum Value
1 = Hold Last State
Default Value
0
OUTA DN FLTVALUE
This parameter determines the state that
Output A assumes when a DeviceNet
network fault occurs and Parameter 67 is set
to “0”.
Parameter Number
68
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-1-6
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Open
Maximum Value
1 = Closed
Default Value
0
OUTA DN IDLSTATE
This parameter, in conjunction with
Parameter 70, defines how Output A will
respond when the DeviceNet network is idle.
When set to “1”, Output A will hold the state
prior to trip occurrence. When set to “0”,
Output A will open or close as determined by
the setting in Parameter 70.
The Dn Flt parameters supersede the Dn Idl
parameters.
Parameter Number
69
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-1-7
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Go to IdlValue (#70)
Maximum Value
1 = Hold Last State
Default Value
0
OUTA DN IDLVALUE
This parameter determines the state that
Output A assumes when the network is idle
and Parameter 69 is set to “0”.
Parameter Number
70
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-1-8
Group
Advanced Setup
Units
—
Minimum Value
0 = Open
Maximum Value
1 = Closed
Default Value
0
OUTB PR FLTSTATE
This parameter, in conjunction with
Parameter 72, defines how Output B will
respond when a trip occurs. When set to “1”,
Output B will continue to operate as
commanded via the network. When set to
“0”, Output B will open or close as
determined by the setting in Parameter 72.
Parameter Number
71
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-2-113
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Go to FltValue (#72)
Maximum Value
1 = Ignore Fault
Default Value
0