Odva fault codes – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 144

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
145
DeviceNet Information Appendix B
ODVA Fault Codes
The following ODVA fault codes are returned by the Control Supervisor Object
instance attribute 13 “TripCode:”
13
Get/Set
COS Mask
WOR
D
—
0
Change of state mask for
DeviceNet
15
Get/Set
AutoBaudEnabl
e
BOOL
0…1
1
1 = Enabled
16
Get/Set
Output
Assembly
USINT
2, 101, 103,
104, 105,
140
103
Output Assembly
instance that is active
17
Get/Set
Input Assembly
USINT
50, 51, 100,
106, 107,
141, 184
100
Input Assembly instance
that is active
18
Get/Set
Program Lock
BOOL
0…1
0
0 = Unlocked
1 = Locked
19
Get/Set
Set To Defaults
BOOL
0…1
0
0 = No action
1 = Reset
20
Get
Device
Configuration
WOR
D
0…7
Bit 0 set = 4 in/2 out
hardware present
Bit 1 set = PTC hardware
present
Bit 2 set = Ground Fault
hardware present
50
Get/Set
PNB COS Mask
WOR
D
0…0xFF
0
Change of State mask
for PNB
Table 64 - DeviceNet Interface Object Common Services
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table 63 - DeviceNet Interface Object Instance Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Min/Max
Defau
lt
Desc.
Table 65 - ODVA Fault Codes
Trip Code
Description
Trip Code
Description
62
Memory Fault
73
Starts/Hour Exceeded
10
Test Trip
102
Comm Fault
11
Remote Trip
103
Comm Idle Fault
23
L1 Loss
108
L2 Undercurrent
24
L2 Loss
109
L3 Undercurrent
25
L3 Loss
110
L1Overcurrent
27
Ground Fault
111
L2Overcurrent