Devicelogix group – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 79

80
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
DeviceLogix Group
COMM OVERRIDE
This parameter is used to enable DeviceLogix
programs to override normal output behavior
in the event of a communication status
change. These events include all states
where the E3 Plus is without an I/O
connection (I/O Connection does not exist,
has timed out, has been deleted, or is
currently idle)
Parameter Number
79
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x1E-1-105
Group
DeviceLogix
Units
—
Minimum Value
0 = Disabled
Maximum Value
1 = Enabled
Default Value
0
NETWORK OVERRIDE
This parameter is used to enable DeviceLogix
programs to override normal output behavior
in the event of a network fault. Network
faults include duplicate MAC ID failures and
bus off conditions.
Parameter Number
80
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x1E-1-104
Group
DeviceLogix
Units
—
Minimum Value
0 = Disabled
Maximum Value
1 = Enabled
Default Value
0
NET OUTPUTS
This parameter monitors network outputs
controlled through DeviceLogix programs.
Parameter Number
81
Access Rule
Get/Set
Data Type
WORD
Object Mapping
0x04-1-3
Group
DeviceLogix
Units
—
Minimum Value
Maximum Value
Default Value
Bits
Function:
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
X
Net Output 0
X
Net Output 1
X
Net Output 2
X
Net Output 3
X
Net Output 4
X
Net Output 5
X
Net Output 6
X
Net Output 7
X
Net Output 8
X
Net Output 9
X
Net Output 10
X
Net Output 11
X
Net Output 12
X
Net Output 13
X
Net Output 14
X
—