beautypg.com

Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 76

background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

77

Programmable Parameters Chapter 5

Table 19 - Output State Matrix for Output Setup Parameters

Commanded
Output State
Prior to Trip

Out X
PR FltState
Setting

Out X
PR FltValue
Setting

Output State
with Active Trip

Last Commanded
Output State during Trip

Output State Following Trip
Reset
(before any new command)

Open

0 = Go to FltValue

0 = Open

Open

Open

Open

Close

Open

-none -

Open

1 = Closed

Closed

Open

Closed

Close

Closed

-none -

Closed

1 = Ignore Fault

As Commanded

As Commanded

As Commanded

Close

0 = Go to FltValue

0 = Open

Open

Open

Open

Close

Open

-none -

Open

1 = Closed

Closed

Open

Closed

Close

Closed

-none -

Closed

1 = Ignore Fault

As Commanded

As Commanded

As Commanded

OUTA PR FLTSTATE

This parameter, in conjunction with
Parameter 66, defines how Output A will
respond when a trip occurs. When set to “1”,
Output A will continue to operate as
commanded via the network. When set to
“0”, Output A will open or close as
determined by the setting of Parameter 66.

Parameter Number

65

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-1-113

Group

DeviceNet I/O

Units

Minimum Value

0 = Go to FltValue (#66)

Maximum Value

1 = Ignore Fault

Default Value

0

OUTA PR FLTVALUE

This parameter determines the state that
Output A assumes when a trip occurs and
Parameter 65 is set to “0”.

Parameter Number

66

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-1-114

Group

DeviceNet I/O

Units

Minimum Value

0 = Open

Maximum Value

1 = Closed

Default Value

0