Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 76
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
77
Programmable Parameters Chapter 5
Table 19 - Output State Matrix for Output Setup Parameters
Commanded
Output State
Prior to Trip
Out X
PR FltState
Setting
Out X
PR FltValue
Setting
Output State
with Active Trip
Last Commanded
Output State during Trip
Output State Following Trip
Reset
(before any new command)
Open
0 = Go to FltValue
0 = Open
Open
Open
Open
Close
Open
-none -
Open
1 = Closed
Closed
Open
Closed
Close
Closed
-none -
Closed
1 = Ignore Fault
—
As Commanded
As Commanded
As Commanded
Close
0 = Go to FltValue
0 = Open
Open
Open
Open
Close
Open
-none -
Open
1 = Closed
Closed
Open
Closed
Close
Closed
-none -
Closed
1 = Ignore Fault
—
As Commanded
As Commanded
As Commanded
OUTA PR FLTSTATE
This parameter, in conjunction with
Parameter 66, defines how Output A will
respond when a trip occurs. When set to “1”,
Output A will continue to operate as
commanded via the network. When set to
“0”, Output A will open or close as
determined by the setting of Parameter 66.
Parameter Number
65
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-1-113
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Go to FltValue (#66)
Maximum Value
1 = Ignore Fault
Default Value
0
OUTA PR FLTVALUE
This parameter determines the state that
Output A assumes when a trip occurs and
Parameter 65 is set to “0”.
Parameter Number
66
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0x09-1-114
Group
DeviceNet I/O
Units
—
Minimum Value
0 = Open
Maximum Value
1 = Closed
Default Value
0