Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 65

66
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
PM - # Starts
This parameter allows the installer to set a
number of starts after which preventative
maintenance should be performed.
Parameter Number
101
Access Rule
Get/Set
Data Type
UINT
Object Mapping
29hex-1-106
Group
Advanced Setup
Units
—
Minimum Value
0
Maximum Value
65535
Default Value
0
GF Warn Delay
This parameter allows the installer to
program a time duration for which a ground
fault condition must exist at the programmed
level prior to the device providing a warning.
Parameter Number
105
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2Chex-1-180
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
0
PM - Oper. Hours
This parameter allows the installer to set the
hours of operation after which preventative
maintenance should be performed.
Parameter Number
102
Access Rule
Get/Set
Data Type
UINT
Object Mapping
29hex-1-107
Group
Advanced Setup
Units
Hours
Minimum Value
0
Maximum Value
65535
Default Value
0
UC Inhibit Time
This parameter sets the time in which the
under current protection is inhibited during a
starting sequence.
Parameter Number
107
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-158
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
1