Connection object – class code 0x05 – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 128

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
129
DeviceNet Information Appendix B
Connection Object – Class
Code 0x05
The following class attributes are supported for the Connection Object:
Three instances of the Connection Object are supported. Instance 1 is the
explicit message connection, instance 2 is the polled I/O connection, and
instance 4 is the Change of State/Cyclic I/O connection.
The following instance 1 (explicit message connection) attributes are supported:
2
Network
Input 7
Network
Input 6
Network
Input 5
Network
Input 4
Network
Input 3
Network
Input 2
Network
Input 1
Network
Input 0
3
Network
Input 15
Network
Input 14
Network
Input 13
Network
Input 12
Network
Input 11
Network
Input 10
Network
Input 9
Network
Input 8
4
Status Parameter A (low)
5
Status Parameter A (high)
6
Status Parameter B (low)
7
Status Parameter B (high)
Table 33 - Instance 111 Data Link Input Assembly Attributes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit3
Bit 2
Bit 1
Bit 0
0
Parameter A Number (low)
1
Parameter A Number (high)
2
Parameter A Data (low)
3
Parameter A Data (high)
4
Parameter B Number (low)
5
Parameter B Number (high)
6
Parameter B Data (low)
7
Parameter B Data (high)
Table 32 - Instance 110 Data Link Output Assembly Attributes
(“PARAM LINK CMD”)
Table 34 - Connection Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1