beautypg.com

Catalog number explanation, Single-/three-phase operation, Protection and warning functions – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 11: Current monitoring parameters, 193 - ec4 b b

background image

12

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 1 Product Overview

Catalog Number
Explanation

Figure 2 - Catalog Number Explanation

Single-/Three-Phase
Operation

The EC4 Current Monitoring Relay is factory-programmed to monitor
three-phase current. The installer can easily change to single-phase operation by
accessing and changing the setting of Parameter 27,

Single/Three Ph. Refer to

Chapter 2 — Installation and Wiring

– for typical motor connections.

Protection and Warning
Functions

The EC4 Current Monitoring Relay provides the following protection and
warning functions:

• L(1-3) Undercurrent
• L(1-3) Overcurrent
• L(1-3) Loss
• Communication Fault/Idle
• Number of Starts (warning only)
• Number of Hours (warning only)

Refer to Chapter 3 — Protective Trip and Warning Functions and Chapter 5
— Programmable Parameters

for further explanation of these functions.

Current Monitoring
Parameters

The EC4 Current Monitoring Relay allows the user to monitor the following
operational data over the DeviceNet network:

• Individual phase currents (in amperes)
• Ground fault current (in amperes)

Refer to Chapter 6 — Current Monitoring Parameters for further information.

193 - EC4 B B

Bulletin
Number

Type
EC4 EC4

Current Rating
(Amps)
P

0.4…2.0

A

1…5

B

3…15

C

5…25

D

9…45

E

18…90

Z

9…5000

Bulletin 100
Contactor Size

B

C09…C23

D

C30…C43

E

C60…C85

Z

Panel Mount, CT fed