Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 130

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
131
DeviceNet Information Appendix B
The following instance 4 (Change of State/Cyclic I/O connection) attributes are
supported:
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = Node address
6
Get
Initial Comm
Characteristics
BYTE
0x21
7
Get
Produced Connection Size UINT
0…8
8
Get
Consumed Connection
Size
UINT
0…8
9
Get/Set
Expected Packet Rate
UINT
in ms
12
Get/Set
Watchdog Action
USINT
0 = Transition to timed out
1 = Auto delete
2 = Auto reset
13
Get
Produced Connection
Path Length
UINT
8
14
Get/Set
Produced Connection
Path
EPATH 21 04 00 25 (assy. inst.) 00 30 03
15
Get
Consumed Connection
Path Length
UINT
8
16
Get/Set
Consumed Connection
Path
EPATH 21 04 00 25 (assy. inst.) 00 30 03
Table 37 - Connection Object Instance 4 Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Value
1
Get
State
USINT
0 = Nonexistent
1 = Configuring
3 = Established
4 = Timed out
2
Get
Instance Type
USINT
1 = I/O Message
3
Get
Transport Class Trigger
BYTE
Cyclic: 0x03
Cyclic Ack Suppressed: 0x00
COS: 0x13
COS Ack Suppressed: 0x10
4
Get
Produced Connection ID
UINT
01101xxxxxx
xxxxxx = Node address
5
Get
Consumed Connection ID
UINT
10xxxxxx010
xxxxxx = Node address
6
Get
Initial Comm
Characteristics
BYTE
0x02 (acknowledged)
0x0F (unacknowledged)
7
Get
Produced Connection Size UINT
0…8
8
Get
Consumed Connection
Size
UINT
0…8
9
Get/Set
Expected Packet Rate
UINT
in ms
Table 36 - Connection Object Instance 2 Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Value