Chapter 7 Diagnostic Parameters

Warn Log 2

This parameter records the warning previous
to Warn Log 1.

Parameter Number

92

Access Rule

Get

Data Type

WORD

Object Mapping

29hex-1-111

Group

Monitor

Units

Minimum Value

See Warning Status Table

Maximum Value

See Warning Status Table

Default Value

0

Warn Log 3

This parameter records the warning previous
to Warn Log 2.

Parameter Number

93

Access Rule

Get

Data Type

WORD

Object Mapping

29hex-1-112

Group

Monitor

Units

Minimum Value

See Warning Status Table

Maximum Value

See Warning Status Table

Default Value

0

Warn Log 4

This parameter records the warning previous
to Warn Log 3.

Parameter Number

94

Access Rule

Get

Data Type

WORD

Object Mapping

29hex-1-113

Group

Monitor

Units

Minimum Value

See Warning Status Table

Maximum Value

See Warning Status Table

Default Value

0

Elapsed Time

This parameter records the hours of motor
operation - the time period that the E3 is
sensing motor current present (motor current
must be greater than 30% of the minimum
current rating.

Parameter Number

95

Access Rule

Get

Data Type

UINT

Object Mapping

29hex-1-100

Group

Monitor

Units

Hours

Minimum Value

0

Maximum Value

65535

Default Value

0

Starts Counter

This parameter records the number of starts -
motor current transitions from zero to
non-zero values (motor current must be
greater than 30% of the minimum current
rating.

Parameter Number

96

Access Rule

Get

Data Type

UINT

Object Mapping

29hex-1-101

Group

Monitor

Units

-

Minimum Value

0

Maximum Value

65535

Default Value

0