L3 UC Warn Level
This parameter sets the under current
warning level for line 3.
Parameter Number
116
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-167
2C
hex
-1-120
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
OC Inhibit Time
This parameter sets the time in which the
over current protection is inhibited during a
starting sequence.
Parameter Number
117
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-168
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
1
L1 OC Trip Level
This parameter sets the over current trip
level for line 1.
Parameter Number
118
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-169
2C
hex
-1-187
➊
Group
Advanced Setup
Units
0.01 Amps
1 Amps
➊
Minimum Value
0.20
Maximum Value
5000
Default Value
L1 OC Trip Delay
This parameter allows the installer to
program a time duration for which an over
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
119
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-170
Group
Advanced Setup
Units
0.1 Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0