PowerFlex 750-Series AC Drives
Control Wiring - Frame 9 and 10 Drives with Cabinet Options
Frame 9 drives are shipped from the factory with control power set to 120V AC. To change
control voltage to 230V AC, move the jumper as shown.
Table 101 - Control Power for Customer Use Voltage Selection - Floor Mount Frames 9 and 10 Drives
Control terminal block TB4 is mounted on the power option module. TB1 referenced in
the illustrations below resides on the main control board. See
Figure 143 - Control Terminal Blocks TB3 and TB4 - Floor Mount Frames 9 and 10 Drives
120V AC, 60Hz, 4.2A (Factory Setting)
230V AC, 50Hz, 2.2A
TB3(H)
T1 (X2)
FU12
600V AC, 3A, Class CC
TB3(H)
TB4(6)
FU12
600V AC, 6A, Class CC
Reactor Thermostat
Thermostat with Reactor - Frame 9 Only
TB4(2)
TB6(2)
TB6(3)
TB4(4)
TB6(4)
TB4(1)
TB4(3)
TB6(1)
TB1(Di 0dc)
TB1(+24V)
TS1
Thermostat without Reactor - Frames 9 and 10
TB6(2) TB4(2) TB6(3)
TB6(4)
TB4(1)
TB4(4)
TB6(1)
TB1(Di 0dc)
TB1(+24V)
TS1
TB3
TB4