Drive device ports – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 228
228
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
PowerFlex 750-Series AC Drives
Drive Device Ports
Connectors, embedded devices, and installed option modules such as I/O,
communication adapters, and DeviceLogix, have unique port number
assignments. Connectors and embedded devices have fixed port numbers that
cannot be changed. Option modules are assigned a port number when installed.
Figure 115 - Drive Device Ports
Port
Device
Description
00
Host Drive
Fixed port for the drive.
01
HIM
Fixed port at HIM cradle connector.
Splitter cable connector provides Port 01 when HIM cradle connector is unused.
02
DPI Port
Handheld or Remote HIM connection.
Splitter cable connection.
03
Splitter Cable
Connects to DPI Port 02.
Provides Port 02 and Port 03.
04…08
Option Modules
Available ports for option modules. Refer to the Option Module Installation
section, beginning on
, for each option’s port recommendations.
Important: Ports 07 and 08 are available on PowerFlex 755 Frame 2 drives and
larger only. PowerFlex 755 Frame 1 drives and 753 drives do not support Ports 07
and 08.
09
Auxiliary Power Supply
Option Module
Designated port for the Auxiliary Power Supply when connected via cable.
(PowerFlex 755 Frame 1 and 753 drives only. See
10
Inverter
Fixed port for Inverter (PowerFlex 755 Frame 8 drives and larger only).
11
Converter
Fixed port for Converter (PowerFlex 755 Frame 8 drives and larger only).
12
Reserved for future use.
13
EtherNet/IP
Fixed port for embedded EtherNet/IP (PowerFlex 755 drives only).
14
DeviceLogix
Fixed port for embedded DeviceLogix.
00
01
03
02
02
13
10, 11, 14
05
09
06
04
08
07