Relay wiring examples, Series i/o module tb1 wiring examples (continued) – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 244
244
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
PowerFlex 750-Series AC Drives
Relay Wiring Examples
Digital Output
Internal supply
20-750-2263C-1R2T
22-Series I/O Module TB1
22-Series I/O Module TB2
• Set Selection
Port X (22-Series I/O Module): P20 [TO0 Sel] = Port 0: P935 [Drive Status 1], bit 7 = Faulted
• View Results
Port X (22-Series I/O Module): P5 [Dig Out Sts]
Digital Output
External supply
20-750-2263C-1R2T
PLC TB
22-Series I/O Module TB2
22-Series I/O Module TB1 Wiring Examples (Continued)
Input/Output
Connection Example
Required Parameter Changes
24VC
+24V
T0
TC
T1
T0
TC
T1
+24V
Common
T0
TC
T1
T0
TC
T1
OR
+24VDC Common
PLC
1756-1B16
IN-0
GND-0
+24VDC Common
PLC
1756-1V16
OR
DC-0+
IN-0
Input/Output
Connection Example
Required Parameter Changes
Relay Output
External supply
753 Main Control Board
• Set Selection
Port 0: P230 [RO0 Sel] = Port 0: P935 [Drive Status 1], bit 7 = Faulted
• View Results
Port 0: P225 [Dig Out Sts]
22-Series I/O Module
• Set Selection
Port X (22-Series I/O Module): P10 [RO0 Sel] = Port 0: P935 [Drive Status 1], bit 7 = Faulted
• View Results
Port X (22-Series I/O Module): P5 [Dig Out Sts]
Power
Source
R0NC
R0C
R0NO
Power
Source
or
R0NO
R0C
R0NC
R1NO
R1C
R1NC