Wall Mount Frames 1…7

Table 27 - Power Jumper Default Configurations

Floor Mount Frames 8…10

Table 28 - Power Jumper Default Configurations

Table 29 - Recommended Power Jumper Configurations Wall Mount Frames 1…7

IMPORTANT

PowerFlex 750-Series drives, Frames 1…7, leave the factory with Jumpers PE-A and
PE-B in one of two possible configurations. Reconfigure these jumpers based on the
power source type available.

Cat. No. Position 11

Jumper PE-A
(MOV / Input Filter Caps)

Jumper PE-B
(DC Bus Common Mode Caps)

A

Connected

Disconnected

J

Connected

Connected

IMPORTANT

PowerFlex 750-Series drives, Frames 8…10, leave the factory with Jumpers PE-A1,
PE-A2 and PE-B in one of two possible configurations. Reconfigure these jumpers
based on the power source type available.

Cat. No. Position 11

Jumper PE-A1
(MOV)

Jumper PE-A2
(Input Filter Caps)

Jumper PE-B
(DC Bus Common Mode Caps)

A

Connected

Connected

Disconnected

J

Connected

Connected

Connected

ATTENTION: Risk of equipment damage exists. The drive power source type must be
accurately determined. Jumpers PE-A, PE-A1, PE-A2 and PE-B must be configured for
the power source type according to the recommendations in

Table 29

.

Power Source Type

Jumper PE-A

(1)

(2)

(MOV / Input Filter Caps)

(1) When MOVs are disconnected, the power system must have its own transient protection to insure known and controlled voltages.
(2) Frame 5…7 Common DC Input drives do not have the PE-A jumper.

Jumper PE-B
(DC Bus Common mode
Caps)

Benefits Of Correct
Configuration on Power
Source Type

Non-Solid Ground
AC fed ungrounded
Impedance grounded
B phase ground
DC fed from an active

converter

Disconnected

Disconnected

Helps avoid severe equipment
damage when ground fault occurs

Solid Ground
AC fed solidly grounded
DC fed from passive rectifier

which has a solidly
grounded AC source

Connected

Connected

UL compliance, Reduced electrical
noise, Most stable operation, EMC
compliance, Reduced voltage
stress on components and motor
bearings