Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 175
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
175
PowerFlex 750-Series AC Drives
21G…E825
LD
950
50
–
–
–
ND
900
50
–
–
–
HD
750
50
–
–
–
21G…E900
LD
1000
65
–
–
–
ND
950
50
–
–
–
HD
800
50
–
–
–
21G…E980
LD
1100
65
–
–
–
ND
1000
65
–
–
–
HD
900
50
–
–
–
(1) These circuit breakers are considered Branch Circuit Protection for the unit if the tap is within 10 ft. of the breaker input.
(2) These are 21G, SCCR ratings with no additional protection provided. Branch circuit protection (fuse) is required based on NEC guidelines for options with P5.
Drive Catalog
Number
Duty
Cycle
Hp
Short Circuit Current Rating (kA)
Circuit Breaker
Only (P3)
(1)
Circuit Breaker with Input Contactor
(P3 with P11)
(1)
Molded Case Switch Only
(P5)
(2)
Molded Case Switch with Input Contactor
(P5 with P11)
(2)
600 Volt AC Input
Drive Catalog
Number
Duty
Cycle
kW
Short Circuit Current Rating (kA)
Circuit Breaker
Only (P3)
Circuit Breaker with Input Contactor
(P3 with P11)
Molded Case Switch Only
(P5)
Molded Case Switch with Input Contactor
(P5 with P11)
690 Volt AC Input
21G…F265
LD
315
30
SCCR rating for 690V input contactor not
available at time of publication.
25
SCCR rating for 690V input contactor not
available at time of publication.
ND
250
30
25
HD
200
30
25
21G…F330
LD
355
30
25
ND
315
30
25
HD
250
30
25
21G…F370
LD
400
30
25
ND
355
30
25
HD
300
30
25
21G…F415
LD
450
30
25
ND
400
30
25
HD
355
30
25
21G…F460
LD
500
25
25
ND
450
30
25
HD
375
30
25
21G…F500
LD
530
25
25
ND
500
25
25
HD
400
30
25
21G…F590
LD
630
35
–
–
–
ND
560
35
–
–
–
HD
450
35
–
–
–
21G…F650
LD
710
35
–
–
–
ND
630
35
–
–
–
HD
500
35
–
–
–
21G…F710
LD
800
35
–
–
–
ND
710
35
–
–
–
HD
560
35
–
–
–
21G…F765
LD
850
35
–
–
–
ND
750
35
–
–
–
HD
630
35
–
–
–
21G…F795
LD
900
35
–
–
–
ND
800
35
–
–
–
HD
710
35
–
–
–
21G…F960
LD
1000
35
–
–
–
ND
900
35
–
–
–
HD
800
35
–
–
–