Powerflex 755 fiber optic interface board, Floor mount frames 8…10 – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 217
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
217
PowerFlex 750-Series AC Drives
PowerFlex 755 Fiber Optic Interface Board
Floor Mount Frames 8…10
Table 45 - Fiber Interface Board Details
Table 46 - P13 Terminal Designations
Table 47 - P14 Terminal Designations
No. Name
Description
➊
Main Control Board Connector
98 pin main control board interface connection.
➋
P13
Connections for user-supplied 24 volt power.
Powers control circuits when main power is removed.
➌
P14
Connections for internal drive-supplied 24 volt power. Connection is
factory wired and must not be modified by the user.
Powers control circuits when main power is connected.
➍
Inverter Connections
Fiber optic ports: P1 = INV1, P2 = INV2, P3 = INV3, P4 = INV4, P5 =
INV5
Power Block
Terminal
Name
Description
AP+
+24 Volt Auxiliary Power
Connections for customer supplied power supply:
24V DC ±10%, 5 A, PELV (Protective Extra Low
Voltage) or SELV (Safety Extra Low Voltage)
AP–
Auxiliary Power Common
Sh
Shield
Terminating point for wire shields.
Power Block
Terminal
Name
Description
1
+24 Volt Power
Connections for drive supplied power.
2
Power Common
➍
➊
P1 P2 P3
➌
➋
P13
AP+
AP–
Sh
1
2