Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 278
278
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
PowerFlex 750-Series AC Drives
Control Wiring - Current Frame 8 Drives with Cabinet Options
Frame 8 drives are shipped from the factory with control power set to 120V AC. To change
control voltage to 230V AC, move the jumper as shown.
Table 99 - Control Power for Customer Use Voltage Selection - Floor Mount Frame 8 Drives
Control terminal block TB4 is mounted on the inside right panel of the cabinet options bay
in current production drives. TB1 referenced in the illustrations below resides on the main
control board. See
.
Table 100 - TB4 Terminal Block Specifications
Figure 142 - Control Terminal Blocks TB3 and TB4 - Floor Mount Frame 8 Drives
120V AC, 60Hz, 4.2A (Factory Setting)
230V AC, 50Hz, 2.2A
Name
Wire Size Range
Torque
Strip
Length
Maximum
Minimum
Maximum
Recommended
Control Terminal Block TB3
4.0 mm
2
(12 AWG)
0.2 mm
2
(24 AWG)
0.5 N•m
(4.5 lb•in)
0.4 N•m
(3.5 lb•in)
7 mm
(0.28 in.)
Control Terminal Block TB4
4.0 mm
2
(12 AWG)
0.5 mm
2
(20 AWG)
0.5 N•m
(4.5 lb•in)
0.4 N•m
(3.5 lb•in)
8 mm
(0.32 in.)
TB3(H)
TB4(7)
FU12
600V AC, 3A, Class CC
TB3(H)
TB4(6)
FU12
600V AC, 6A, Class CC
Input/Output Contactor with or without X1 Option
TS1
Thermostat
TB6(1)
TB4(4)
TB4(10)
TB6(4)
TB6(3)
TB4(5)
TB6(2)
TB1(+24V)
TB1(Di 0dc)
13
14
TB3(1)
TB3(4)
M2/M4
21
22
TB3(2)
TB3(3)
M2/M4
Optional Devices
M2/M4
TB4(3)
A1
A2
TB4(2)
Contactor without X1 Option
M2/M4
TB4(3)
A1
A2
TB4(2)
Contactor with X1 Option
Customer Supplied
Control Circuit
TB3
TB4