beautypg.com

Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 278

background image

278

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Control Wiring - Current Frame 8 Drives with Cabinet Options

Frame 8 drives are shipped from the factory with control power set to 120V AC. To change
control voltage to 230V AC, move the jumper as shown.

Table 99 - Control Power for Customer Use Voltage Selection - Floor Mount Frame 8 Drives

Control terminal block TB4 is mounted on the inside right panel of the cabinet options bay
in current production drives. TB1 referenced in the illustrations below resides on the main
control board. See

page 213

.

Table 100 - TB4 Terminal Block Specifications

Figure 142 - Control Terminal Blocks TB3 and TB4 - Floor Mount Frame 8 Drives

120V AC, 60Hz, 4.2A (Factory Setting)

230V AC, 50Hz, 2.2A

Name

Wire Size Range

Torque

Strip
Length

Maximum

Minimum

Maximum

Recommended

Control Terminal Block TB3

4.0 mm

2

(12 AWG)

0.2 mm

2

(24 AWG)

0.5 N•m
(4.5 lb•in)

0.4 N•m
(3.5 lb•in)

7 mm
(0.28 in.)

Control Terminal Block TB4

4.0 mm

2

(12 AWG)

0.5 mm

2

(20 AWG)

0.5 N•m
(4.5 lb•in)

0.4 N•m
(3.5 lb•in)

8 mm
(0.32 in.)

TB3(H)

TB4(7)

FU12

600V AC, 3A, Class CC

TB3(H)

TB4(6)

FU12

600V AC, 6A, Class CC

Input/Output Contactor with or without X1 Option

TS1

Thermostat

TB6(1)

TB4(4)

TB4(10)

TB6(4)

TB6(3)

TB4(5)

TB6(2)

TB1(+24V)

TB1(Di 0dc)

13

14

TB3(1)

TB3(4)

M2/M4

21

22

TB3(2)

TB3(3)

M2/M4

Optional Devices

M2/M4

TB4(3)

A1

A2

TB4(2)

Contactor without X1 Option

M2/M4

TB4(3)

A1

A2

TB4(2)

Contactor with X1 Option

Customer Supplied

Control Circuit

TB3

TB4

This manual is related to the following products: