Table 50, Table 51, Dc precharge board – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual
Page 220: Cabinet door interlock and door switch

220
Rockwell Automation Publication 750-IN001N-EN-P - April 2014
PowerFlex 750-Series AC Drives
DC Precharge Board
The DC precharge board provides sensing of bus voltage, monitoring of bus fuses
and control over all precharge hardware.
Table 50 - TB3 Terminal Designations
Cabinet Door Interlock and Door Switch
The Common DC Input drive supports the installation of a door interlock
solenoid and door switch.
Table 51 - TB4 Terminal Designations
Disconnect Switch (SW2) Operation
Fixed I/O
Terminal
Name
Description
1
I/O 24V
Drive supplied 24V DC I/O power.
2
I/O 24V COMMON
3
EXT. PRCHRG CLOSE/OPEN INPUT+
External precharge close/open input.
4
EXT. PRCHRG CLOSE/OPEN INPUT-
5
EXT. PRCHRG INHIBIT INPUT+
External precharge inhibit input.
6
EXT. PRCHRG INHIBIT INPUT-
7
RESET FAULTS INPUT +
Reset faults input.
8
RESET FAULTS INPUT -
9
PRECHARGE COMPLETE NO
Precharge complete normally open input
10
PRECHARGE COMPLETE COM
11
FAULT OUT NC
Normally closed contact output.
Normally open contact output.
12
FAULT OUT NO
13
FAULT OUT COM
Factory Jumper Settings:
• TB3-1 and TB3-3
• TB3-1 and TB3-5
• TB3-2 and TB3-4
• TB3-2 and TB3-6
IMPORTANT: Do not remove the factory installed jumpers.
Fixed I/O
Terminal
Name
Description
1
DOOR SWITCH CLOSED
Normally open door switch.
Door switch input connection.
Remove TB4-1 to TB4-2 jumper to wire switch.
2
I/O 24V
Drive supplied 24V DC power.
Door switch supply or power connection.
3
240 VAC NEUTRAL
Solenoid neutral connection.
4
240 VAC HOT DOOR INTERLOCK
SOLENOID
Drive supplied 240V AC power.
Solenoid hot connection.
SW2 is On
Door Closed
Door Open
for location.
Solenoid and door switch
circuits are energized.
Alarm is indicated.
1
2
3
4
5
6
7
8
9
10
11
12
13
1
2
3
4