Appendix D. Status Table

The CR9000X status table contains current system operating status information that can be accessed from
the running CR9000X program or monitored by PC software. Status Table information is easily viewed
by going to LoggerNetTM / PC400 / RTDAQ / PC200W: (| Datalogger | Station Status). However, be
aware that information presented in this Station Status window is not automatically updated. Click the
refresh button each time an update is desired. Alternatively, use the Numeric displays of the connect
screen to show critical values and have these update automatically, or use Devconfig, which polls the
status table at regular intervals without use of a refresh button.

Table D-1 lists the parameters in the Status table with a brief explanation of each.

Table D-1, Status Table Parameters


Field Name

Variable

Type


Description

RecNum

Long

Record number for this set of data from the Status Table.

TimeStamp

String

Time this record was generated.

OSVersion

String

Operating system installed in logger.

OSDate

String

Date that the Operating System was created.

OSSignature

Integer

Operating System Signature

SlotSrNbr(#) Integer

Shows the serial number of the module in the designated slot #.

SlotRev(#)

Float

Shows the serial number of the module in the designated slot #.

StationName

String

The Station Name of the data logger. This value is stored in the logger's
memory.

ProgName

String

Name of the program that is currently running in the data logger.

StartTime

Time

Time that the running program started running.

RunSignature

Float

Signature of the compiled binary data structure for the current program. Value
is independent of comments added or non-functional changes to the program.
Often changes with operating system changes.

DLDSignature

Float

Signature of the current running program file including comments. Does not
change with operating system changes.

SlotModelNbr

String

Type of Module located in slot #.

Battery(1)

Float

Voltage of the 3.3 volt lithium battery. Replace the lithium battery if <2.7V.

Battery(2)

Float

Voltage of the main 12 volt lead acid battery.

CompileResults

String

Contains error messages generated by compilation or during run time. Returns
"Compiled OK" if there was not any problems with the compilation of the
program.

StartUpCode

Integer

Displays the program Start-Up Code with results shown below:

Returned Code
Value

Interpretation

0

Current program running from power-up condition.

1

A watchdog reset the data logger.

2 - 7

A software time-out watchdog error occurred.

8

An attempt to write to flash memory failed.

9-19

An instruction hang-up watchdog error occurred.

20

A PC Card watchdog error occurred.