Section 7. Measurement Instructions

7-31

SDMSIO4 (Dest, Reps, Address, Mode, Command, FirstOp, SecOp,

ValuesPerRep, Mult, Offset)

This Instruction communicates with theSDM-SIO4 Serial Input Multiplexer.
See the SDM-SIO4 Manual for details.

Parameter

& Data Type

Enter

SDMSIO4 PARAMETERS

Dest

Variable or Array

The Variable in which to store the results of the instruction or, when the instruction is used

to send data, this array becomes the data to send. When Reps or multiple values per rep

are used, the results are stored in an array with the variable name.

The Dest array must be dimensioned to have elements for Reps multiplied by Values per

Rep.

Reps

Constant

The number of repetitions for the measurement or instruction.

Address

Constant

The address for the SDM-SIO4 (0-14)

Mode

The SIO4 port the instruction applies to.

Constant

Code Port

1

Send/Receive Port 1

2

Send/Receive Port 2

3

Send/Receive Port 3

4

Send/Receive Port 4

5

Send to all four ports (global)

Command,

FirstOp, SecOp

Constants1

Commands to SDM-SIO4. See SDM-SIO4 Manual

ValuesPerRep

Constant

How many values to send or receive

Mult, Offset

Constant,

Variable, Array,

or Expression

A multiplier and offset by which to scale the results. A multiplier of one and an offset of 0

are necessary to store the values as received. For example, the TCDiff instruction

measures a thermocouple and outputs temperature in degrees C. A multiplier of 1.8 and an

offset of 32 will convert the temperature to degrees F.

SDMSW8A (Dest, Reps, SDMAddress, FunctOp, SW8AStartChan, Mult,

Offset)

The SDMSW8A instruction is used to control the SDM-SW8A Eight-Channel
Switch Closure module, and store the results of its measurements to a variable
array.

This instruction must NOT be placed inside a conditional
statement or in a SubScan.

NOTE