beautypg.com

Minimum (reps, source, datatype, disablevar, time), Median parameters, Minimum parameters – Campbell Scientific CR9000X Measurement and Control System User Manual

Page 210

background image

Section 6. Data Table Declarations and Output Processing Instructions

Parameter &
Data Type

Enter

MEDIAN PARAMETERS

Reps
Constant

Number of variables for which to calculate a median (separate median will be calculated
for each variable). If Reps parameter is greater than 1, an array must be specified for
Source. If not, a Variable Out of Bounds error will be returned when the program is
compiled.

Source Variable
Array

The name of the variable(s) for which the median(s) should be calculated.

MaxN Variable
Array

The maximum number of values, for each median, that the datalogger should maintain in
memory for the instruction, from which the median will be calculated.

DataType

A code to select the data storage format.

Read More: See Section 4.2.4.4 Data Types

Constant

Alpha Code

Numeric Code

Data Format

IEEE4

24

IEEE 4 byte floating point

FP2

7

Campbell Scientific 2 byte floating point

UINT2

21

2 Byte unsigned integer

Long

20

4 Byte Integer value

DisableVar

A non-zero value will disable intermediate processing: input is not included in the
Covariance.

Constant,

Value Result

Variable, or

0

Process current input

Expression

≠ 0

Do not process current input

Minimum (Reps, Source, DataType, DisableVar, Time)

This instruction stores the Minimum value that occurs in the specified Source
variable over the output interval. Time of minimum value(s) is optional output
information, which is selected by entering the appropriate code in the time
parameter. NANs are ignored by this output processing instruction.

Parameter
& Data Type

Enter

MINIMUM PARAMETERS

Reps

Constant

The number of minimum values to determine. When repetitions are greater than 1, the source must be an
array..

Source

Variable

The name of the Variable that is the input for the instruction.

DataType

A code to select the data storage format. Read More: See Section 4.2.4.4 Data Types

Constant

Alpha Code

Numeric Code

Data Format

IEEE4

24

IEEE 4 byte floating point

FP2

7

Campbell Scientific 2 byte floating point

UINT2

21

2 Byte unsigned integer

Long

20

4 Byte Integer value

DisableVar

Constant,
Variable, or

A non-zero value will disable intermediate processing. Normally 0 is entered so all inputs are processed.
For example, when the disable variable is

≠0 the current input is not checked for a new minimum. The

minimum that is eventually stored is the minimum that occurred while the disable variable was 0.

Expression

Value Result

0

Process current input

≠ 0

Do not process current input

Time
Constant

Option to store time of Minimum. When time is output, the minimum values for all repetitions are
output first followed by the times at which they occurred.

Value Result

0

Do not store time

1

Store time

Time of max is stored in the NSec format

6-26