'\\\\\\\\\\\\\\\\\\\\ DECLARE VARIABLES /////////////////////////////
SlotConfigure(9050,9060)
Const Reps = 3
'Set program to measure 3 strain gauges
Const BrConfig = -4
'Block1 gauge code for Full bridge strain, Bending
Dim
I
'Declare I as a variable
Public NumAvg, CalFileLoaded, Flag(8)
'Variables that are arguments in the Zero Function
Public ModeZero, ZeroReps, Index0,RepS
Public RawmVperV(Reps)
Public ZeroMvperV(Reps)
'Variables that are arguments in the Shunt Function
Public ModeShunt, KnownRes(Reps), IndexS
Public MeasureVar_uS(Reps)
Public GF_Adj(Reps), GF_Raw(Reps)
'---------------------------- Tables----------------------------
DataTable(Table1,True,-1)
'Trigger, auto size
DataInterval(0,50,mSec,100)
Average(Reps,MeasureVar_uS(),IEEE4,False)
EndTable
DataTable(CalHist,NewFieldCal,50)
SampleFieldCal
EndTable
'\\\\\\\\\\\\\\\\\\\\\\\\\\\\ PROGRAM ////////////////////////////
BeginProg
NumAvg = 10
'Initialize the number of values to average for the calibrations
IndexS =
1
'Initialize shunt Index to 1
Index0
= 1
'Initialize zero index to 1
Zeroreps = Reps
'Initialize ZeroReps to full size of array
RepS = 1
'Initialize RepS to 1 (FieldCalStrain Shunt operation)
'Set Gage Factors
GF_Raw(1) = 2.1 : GF_Raw(2) = 2.1 : GF_Raw(3) = 2.13
For
I = 1
To
Reps
'Initialize the Adj Gage Factors to the raw GF value
GF_Adj(I) = GF_Raw(I)
'The adj Gage factors are used in the calculation of uStrain
Next
I
' If a calibration has been done, the following will load the zero or Adjusted GF from the Calibration file
CalFileLoaded
=
LoadFieldCal(1)
Scan(10,mSec,100,0)
BrFull(RawmvperV(),Reps,mV50,4,1,5,1,1,5000,True,True,40,100,1,0)
StrainCalc(MeasureVar_uS(),Reps,RawmvperV(),ZeroMvperV(),BrConfig,GF_Adj(),0)
'Strain calculation
If
Flag(8) then
ZeroReps = Reps
'Set Reps to zero complete measurement array
Index0
= 1
'Verify that the index is at the beginning of the array
ModeZero = 1
'Set the Mode for the zero function to 1 to start the zero process
Flag(8)
= 0
'Set the zero flag back to low
Endif
'FieldCalStrain(Zeroing,Mvar, reps, GF_adj,Zeromv_V, ModeVar,KnownVar,index,Numavg,GF_Raw,uS)
FIELDCALSTRAIN
(10,RawmvperV(),ZeroReps,0,ZeroMvperV(),ModeZero,0,index0,NumAvg,0,MeasureVar_uS())
'FieldCalStrain(Shunt,Mvar, reps,GF,Zerooffset, ModeVar, KnownVar,index,Numavg,GF_Raw,uStrain)
FIELDCALSTRAIN
(43,MeasureVar_uS(),RepS,GF_Adj(),0,ModeShunt,KnownRes,IndexS,NumAvg,GF_Raw(),0)
CallTable Table1
CallTable CalHist
Next Scan
EndProg