Parameter
& Data Type

Enter

FFTFILT PARAMETERS

FiltOption
Constant

The sample ratio for the measurement (how many measurements are made within one cycle of the
highest frequency in the pass band). The sample ratio determines the top of the pass-band (F

PASS

)

and the beginning of the stop-band (F

STOP

) of the anti-aliasing low-pass filter relative the sample

rate (F

SAMPLE

). The sample rate is the inverse the scan interval in the CRBASIC program.

FiltOption must be the same for all channels of a single CR9052DC Filter Module. The CR9052
normally replaces out-of-range measurements with not-a-number (NaN) which is displayed in
RTDaq's realtime windows as Range?. Out-of-range measurements may be replaced by the
analog-to-digital converter saturation value by adding 1000 to the FiltOption codes shown
below.

Numeric Code

Sampling Ratio

F

PASS

F

STOP

2 2.5

F

SAMPLE

/2.5

F

SAMPLE

/2.01

5 5

F

SAMPLE

/5

F

SAMPLE

/3.37

10 10

F

SAMPLE

/10

F

SAMPLE

/5.08

20 20

F

SAMPLE

/20

F

SAMPLE

/6.81

1* 2.155

23.2 Khz

26.8 kHz

FiltOption 1 is available only when FsampRate is 50 kHz. At this sample rate, no additional

filtering beyond that provided by the CR9052DC hardware is required to anti-alias the data.
Because the CR9052DC processor is not performing additional anti-alias filtering, this
FiltOption increases the CR9052DC’s FFT throughput. To achieve spectra from seamless
snapshots with FsampRate equal to 50 kHz on six channels, FiltOption must be 1.

Excitation

Constant

The continuous, dc, output level for the excitation channel(s). If Reps is greater than one, then the
CR9052 Module drives the same excitation level on sequential excitation outputs.

Numeric Code

Alpha Code

Output Level

IEPE Freq. Response

CR9052IEPE

900 (905)

None

None

τ

= 0.5 Sec (

τ

= 5.0 Sec)

CR9052IEPE

605

None

Constant 6 mA

0.3 Hz to 20 kHz (

τ

= 5.0 Sec)

CR9052IEPE

405

None

Constant 4 mA

0.3 Hz to 20 kHz (

τ

= 5.0 Sec)

CR9052IEPE

205

None

Constant 2 mA

0.3 Hz to 20 kHz (

τ

= 5.0 Sec)

CR9052IEPE

600

None

Constant 6 mA

3.0 Hz to 20 kHz (

τ

= 0.5 Sec)

CR9052IEPE

400

None

Constant 4 mA

3.0 Hz to 20 kHz (

τ

= 0.5 Sec)

CR9052IEPE

200

None

Constant 2 mA

3.0 Hz to 20 kHz (

τ

= 0.5 Sec)

CR9052DC

7

V10

Constant 10 V DC

CR9052DC

5

None

Constant 5 V DC

CR9052DC

2

None

Constant 10 mA

CR9052DC

1

None

None

Mult

Constant,Variable,
Array, Expression

A factor by which to multiply the raw time-series voltage measurements. Mult

-1

provides the

reference value for the deciBell (dB) spectral option.

FsampRate

Constant

The sample rate in samples per second, at which the CR9052 will collect time series data before
performing the FFT.

FsampRate must be the same for all channels in a CR9052 module

.

Some

of the available rates are shown below:

FsampRate

Sample Rate

Sample Interval

50000

50

kHz

20

μs

25000

25

kHz

40

μs

10000

10

kHz

100

μs

5000

5

kHz

200

μs

2500

2.5

kHz

400

μs

1000 1

kHz 1

ms

500

500

Hz

2

ms

250

250

Hz

4

ms

100

100

Hz

10

ms

50

50

Hz

20

ms