Alpha code, Code, Tcdiff parameters – Campbell Scientific CR9000X Measurement and Control System User Manual
Page 230

Section 7. Measurement Instructions
7-6
Parameter
Enter
TCDIFF PARAMETERS
Dest
Var. or Array
The Variable in which to store the results of the instruction. When Reps are used the results are stored in
an array with the variable name. An array must be dimensioned to have elements for all of the Reps.
Reps
Constant
The number of repetitions for the measurement.
Range*
The voltage range for the measurement. TCDiff raw output is Celsius.
Constant
± 5 Volt Analog Input
Module
± 50 Volt Analog Input
Module
CR9058E* Isolation Module
Alpha
Code
Num
Code
R *
Option
Code
Voltage
Range
(±mV)
Alpha
Code
Num
Code
R *
Option
Code
Voltage
Range
±
Alpha
Code
Num
Code
R * Option
Code
Voltage Range
mV5000
0 100
5000 V50 6
N/A
50 V
V60
24
N/A
± 60 V
mV1000
1 101
1000 V10
7
N/A
10 V
V20
25
N/A
± 20 V
mV200
4 104
200 V2
10 N/A
2 V
V2
10
N/A
± 2 V
mV50
5
105
50
mV500 11 N/A
500 mV
V2C
22
N/A
± 2 V
mV200C 16
116
200
Alpha Codes ending with a C signify that the channel will be pulled into
See Section
3.2.2 for
more info on
the C & R
range code
options.
mV50C
17
117
50
Operational Input Voltage Limits & checked for open input.
See Section 3.1.2.2 Differential Voltage Range for details.
ASlot
Constant
The number of the slot that holds the Analog Input Module to be used for the measurement.
DiffChan
Constant
The differential channel number on which to make the first measurement. When Reps are used, subsequent
measurements will be automatically made on the sequential differential channels. Enter a negative number to
dwell on that channel for the number of measurements specified by the Reps parameter (except for CR9058E).
TCType
The code for the thermocouple type.
Constant
Alpha Code
Numeric Code
Thermocouple Type
TypeT
0
Copper Constantan
TypeE
1 Chromel
Constantan
TypeK
2 Chromel
Alumel
TypeJ
3 Iron
Constantan
TypeB
4 Platinum
Rhodium
TypeR
5 Platinum
Rhodium
TypeS
6 Platinum
Rhodium
TypeN
7 Nicrosil-Nisil
(NiCRSi-NiSiMg)
TRef
Variable
The name of the variable that is the reference temperature for the thermocouple measurements.
RevDiff
Constant
Option to reverse inputs to cancel offsets. The sign corrected average of these measurements is used in
the result. This technique cancels voltage offsets in the measurement circuitry but requires twice as
much time to complete the measurement. (CR9058E: All channels on a module must have same setting.)
Value
0
Inputs are not reversed.
1
A second measurement is made after reversing the inputs
SettlingTime
Constant
The time in microseconds to delay between setting up a measurement (switching to the channel, setting
the excitation) and making the measurement (10 microsecond resolution).
See Section 3.1.3 Signal Settling Time. Enter 0 when using the CR9058E (Settling Time not used).
Entry
Voltage
Range
Delay
CR9055 Voltage
Range
Delay
0
± 50 mV
20 µS (default)
± 0.5V
40 µS (default)
0
± 200 mV
20 µS (default)
± 2 V
40 µS (default)
0
± 1000 mV
10 µS (default)
± 10 V
30 µS (default)
0
± 5000 mV
10 µS (default)
± 50 V
30 µS (default)
> 0
all
Truncate to closest 10µS
all
Truncate to closest 10 µS
Integ
Constant
The integration time in microseconds for each of the channels measured (10 microseconds resolution).
CR9058E*:100 microsecond resolution. All channels on a CR9058 module must have same integration.
Mult, Offset
Constant, Var,
Array, or
Expression
A multiplier and offset by which to scale the raw results of the measurement. The raw output for the
TCDiff
instruction is in degrees C. A multiplier of 1.8 and an offset of 32 will convert the temperature
to degrees F.