Section 7. Measurement Instructions

7-6

Parameter

Enter

TCDIFF PARAMETERS

Dest

Var. or Array

The Variable in which to store the results of the instruction. When Reps are used the results are stored in
an array with the variable name. An array must be dimensioned to have elements for all of the Reps.

Reps

Constant

The number of repetitions for the measurement.

Range*

The voltage range for the measurement. TCDiff raw output is Celsius.

Constant

± 5 Volt Analog Input
Module

± 50 Volt Analog Input
Module

CR9058E* Isolation Module

Alpha

Code

Num

Code

R *

Option

Code

Voltage

Range

(±mV)

Alpha

Code

Num

Code

R *

Option

Code

Voltage

Range

±

Alpha

Code

Num

Code

R * Option

Code

Voltage Range

mV5000

0 100

5000 V50 6

N/A

50 V

V60

24

N/A

± 60 V

mV1000

1 101

1000 V10

7

N/A

10 V

V20

25

N/A

± 20 V

mV200

4 104

200 V2

10 N/A

2 V

V2

10

N/A

± 2 V

mV50

5

105

50

mV500 11 N/A

500 mV

V2C

22

N/A

± 2 V

mV200C 16

116

200

Alpha Codes ending with a C signify that the channel will be pulled into

See Section

3.2.2 for

more info on

the C & R

range code

options.

mV50C

17

117

50

Operational Input Voltage Limits & checked for open input.
See Section 3.1.2.2 Differential Voltage Range for details.

ASlot

Constant

The number of the slot that holds the Analog Input Module to be used for the measurement.

DiffChan

Constant

The differential channel number on which to make the first measurement. When Reps are used, subsequent
measurements will be automatically made on the sequential differential channels. Enter a negative number to
dwell on that channel for the number of measurements specified by the Reps parameter (except for CR9058E).

TCType

The code for the thermocouple type.

Constant

Alpha Code

Numeric Code

Thermocouple Type

TypeT

0

Copper Constantan

TypeE

1 Chromel

Constantan

TypeK

2 Chromel

Alumel

TypeJ

3 Iron

Constantan

TypeB

4 Platinum

Rhodium

TypeR

5 Platinum

Rhodium

TypeS

6 Platinum

Rhodium

TypeN

7 Nicrosil-Nisil

(NiCRSi-NiSiMg)

TRef

Variable

The name of the variable that is the reference temperature for the thermocouple measurements.

RevDiff

Constant

Option to reverse inputs to cancel offsets. The sign corrected average of these measurements is used in
the result. This technique cancels voltage offsets in the measurement circuitry but requires twice as
much time to complete the measurement. (CR9058E: All channels on a module must have same setting.)

Value

0

Inputs are not reversed.

1

A second measurement is made after reversing the inputs

SettlingTime

Constant

The time in microseconds to delay between setting up a measurement (switching to the channel, setting
the excitation) and making the measurement (10 microsecond resolution).
See Section 3.1.3 Signal Settling Time. Enter 0 when using the CR9058E (Settling Time not used).


Entry

Voltage
Range


Delay

CR9055 Voltage
Range


Delay

0

± 50 mV

20 µS (default)

± 0.5V

40 µS (default)

0

± 200 mV

20 µS (default)

± 2 V

40 µS (default)

0

± 1000 mV

10 µS (default)

± 10 V

30 µS (default)

0

± 5000 mV

10 µS (default)

± 50 V

30 µS (default)

> 0

all

Truncate to closest 10µS

all

Truncate to closest 10 µS

Integ

Constant

The integration time in microseconds for each of the channels measured (10 microseconds resolution).
CR9058E*:100 microsecond resolution. All channels on a CR9058 module must have same integration.

Mult, Offset

Constant, Var,
Array, or
Expression

A multiplier and offset by which to scale the raw results of the measurement. The raw output for the
TCDiff

instruction is in degrees C. A multiplier of 1.8 and an offset of 32 will convert the temperature

to degrees F.