Section 7. Installation

99

 

Figure 39: DevConfig Deployment tab

Datalogger Sub-Tab

Serial Number displays the CR1000 serial number. This setting is set at the

factory and cannot be edited.

OS Version displays the operating system version that is in the CR1000.
Station Name displays the name that is set for this station. The default

station name is the CR1000 serial number.

PakBus® Address allows users to set the PakBus® address of the

datalogger. The allowable range is between 1 and 4094. Each PakBus®
device should have a unique PakBus® address. Addresses >3999 force other
PakBus® devices to respond regardless of their respective PakBus® settings.
See the PakBus® Networking Guide (available from Campbell Scientific) for
more information.

Security - See Security

(p. 70).

ComPorts Settings Sub-Tab

As shown in figure DevConfig Deployment | ComPorts Settings Tab

(p. 101),

the

following settings are available for comports.

Read More! PakBus

®

Networking Guide available at www.campbellsci.com.

Selected Port specifies the datalogger serial port to which the beacon interval

and hello-setting values are applied.