Section 7. Installation

202 

 

 

7.8.8.2 I/O Ports

The CR1000 supports two-way serial communication with other instruments
through ports listed in table CR1000 Serial Ports

(p. 202).

A serial device will often

be supplied with a nine-pin D-type connector serial port. Check the manufacture's
pinout for specific information. In most cases, the standard nine-pin RS-232
scheme is used. If that is the case then,

• Connect sensor RX (receive, pin 2) to datalogger Tx (transmit, channel C1,

C3, C5, C7).

• Connect sensor TX (transmit, pin 3) to datalogger Rx (receive, channel C2,

C4, C6, C8).

• Connect sensor ground (pin 5) to datalogger ground (G terminal)

Note Rx and Tx lines on nine-pin connectors are sometimes switched by the
manufacturer.

Table 31. CR1000 Serial Ports

Serial Port

Voltage Level

Logic

RS-232 (9-pin)

RS-232

Full-duplex asynchronous RS-232

CS I/O (9-pin)

TTL

Full-duplex asynchronous RS-232

COM1 (C1 - C2)

TTL Full-duplex

asynchronous RS-232/TTL

COM2 (C3 - C4)

TTL Full-duplex

asynchronous RS-232/TTL

COM3 (C5 - C6)

TTL Full-duplex

asynchronous RS-232/TTL

COM4 (C7 - C8)

TTL Full-duplex

asynchronous RS-232/TTL

C1

5 Vdc

SDI-12

C3

5 Vdc

SDI-12

C5

5 Vdc

SDI-12

C7

5 Vdc

SDI-12

C1, C2, C3

5 Vdc

SDM (used with Campbell Scientific

peripherals only)

 

7.8.8.3 Protocols

PakBus is the protocol native to the CR1000 and transparently handles routine
point-to-point and network communications among PCs and Campbell Scientific
dataloggers. Modbus and DNP3 are industry-standard networking SCADA
protocols that optionally operate in the CR1000 with minimal configuration by the
user. PakBus®, Modbus, and DNP3 operate on the RS-232, CS I/O, and four
COM ports. SDI-12 is a protocol used by some smart sensors that requires
minimal configuration on the CR1000.

Read More! See SDI-12 Recording

(p. 323),

SDI-12 Sensor Support

(p. 172),

PakBus

Overview

(p. 351),

DNP3

(p. 364),

and Modbus

(p. 367).

Many instruments require non-standard protocols to communicate with the
CR1000.