2 i/o ports, 3 protocols, Table 31. cr1000 serial ports – Campbell Scientific CR1000 Measurement and Control System User Manual
Page 202

Section 7. Installation
202
7.8.8.2 I/O Ports
The CR1000 supports two-way serial communication with other instruments
through ports listed in table CR1000 Serial Ports
(p. 202).
A serial device will often
be supplied with a nine-pin D-type connector serial port. Check the manufacture's
pinout for specific information. In most cases, the standard nine-pin RS-232
scheme is used. If that is the case then,
• Connect sensor RX (receive, pin 2) to datalogger Tx (transmit, channel C1,
C3, C5, C7).
• Connect sensor TX (transmit, pin 3) to datalogger Rx (receive, channel C2,
C4, C6, C8).
• Connect sensor ground (pin 5) to datalogger ground (G terminal)
Note Rx and Tx lines on nine-pin connectors are sometimes switched by the
manufacturer.
Table 31. CR1000 Serial Ports
Serial Port
Voltage Level
Logic
RS-232 (9-pin)
RS-232
Full-duplex asynchronous RS-232
CS I/O (9-pin)
TTL
Full-duplex asynchronous RS-232
COM1 (C1 - C2)
TTL Full-duplex
asynchronous RS-232/TTL
COM2 (C3 - C4)
TTL Full-duplex
asynchronous RS-232/TTL
COM3 (C5 - C6)
TTL Full-duplex
asynchronous RS-232/TTL
COM4 (C7 - C8)
TTL Full-duplex
asynchronous RS-232/TTL
C1
5 Vdc
SDI-12
C3
5 Vdc
SDI-12
C5
5 Vdc
SDI-12
C7
5 Vdc
SDI-12
C1, C2, C3
5 Vdc
SDM (used with Campbell Scientific
peripherals only)
7.8.8.3 Protocols
PakBus is the protocol native to the CR1000 and transparently handles routine
point-to-point and network communications among PCs and Campbell Scientific
dataloggers. Modbus and DNP3 are industry-standard networking SCADA
protocols that optionally operate in the CR1000 with minimal configuration by the
user. PakBus®, Modbus, and DNP3 operate on the RS-232, CS I/O, and four
COM ports. SDI-12 is a protocol used by some smart sensors that requires
minimal configuration on the CR1000.
Read More! See SDI-12 Recording
(p. 323),
SDI-12 Sensor Support
(p. 172),
PakBus
Overview
(p. 351),
DNP3
(p. 364),
and Modbus
(p. 367).
Many instruments require non-standard protocols to communicate with the
CR1000.