Appendix B. Status Table and Settings

533

 

Table 121. Status-Table Fields and Descriptions

Fieldname Description

Variable

Type

Default

Range

Edit?

Info

Type

MeasureTime

Time (μs) required to make
the measurements in this
scan, including integration
and settling times. Processing
occurs concurrent with this
time so the sum of measure
time and process time is not
the time required in the scan
instruction. This is a static
value calculated at compile
time. Assumes all
measurement instructions
will run each scan.

Integer

Status

ProcessTime

Processing time (μs) of the
last scan. Time is measured
from the end of the EndScan
instruction (after the
measurement event is set) to
the beginning of the EndScan
(before the wait for the
measurement event begins)
for the subsequent scan.
Calculated dynamically (on
the fly).

Integer

Status

MaxProcTime

Maximum time (μs) required
to run through processing for
the current scan. This value
is reset when the scan exits.
Calculated dynamically (on
the fly).

Integer

Yes
Reset by
changing to 0

Status

BuffDepth

Shows the current Pipeline
Mode processing buffer
depth., which indicates how
far processing is currently
behind measurement.

MaxBuffDepth

Gives the maximum number
of buffers processing lagged
measurement.

LastSystemScan8

The last time the background
calibration executed.

Integer array

Status

LastSlowScan9

The last time SlowSequence
scan(s) executed.

Integer array

Status

SystemProcTime8,12

The time (μs) required to
process the background
calibration.

Integer array

Status

SlowProcTime9,12

The time (μs) required to
process SlowSequence
scan(s).

Integer array

Status

MaxSystemProcTime8,
13

The maximum time (μs)
required to process the
background calibration.

Integer array

Status