CRBasic Example 33. Using Alternate Concurrent Command (aC)
'Code to use when back to back SDI-12 concurrent measurement commands not desired
'Main Program
BeginProg
'Preset first measurement command to C!
For
X = 1
To
4
cmd(X) = "C!"
Next
X
'Set 5 s scan rate
Scan
(5,Sec,0,0)
'Other measurements here
'Set 5 minute measurement rate
If
TimeIntoInterval
(0,5,Min)
Then
RunSDI12 = True
'Begin measurement sequence
If
RunSDI12 = True
Then
For
X = 1
To
4
Temp_Tmp(X) = 2e9
'when 2e9 changes, indicates a change
Next
X
'Measure SDI-12 sensors
SDI12Recorder
(Temp_Tmp(1),1,0,cmd(1),1.0,0)
SDI12Recorder
(Temp_Tmp(2),1,1,cmd(2),1.0,0)
SDI12Recorder
(Temp_Tmp(3),1,2,cmd(3),1.0,0)
SDI12Recorder
(Temp_Tmp(4),1,3,cmd(4),1.0,0)
'Control Measurement Event
For
X = 1
To
4
If
cmd(X) = "C!"
Then
Retry(X) = Retry(X) + 1
If
Retry(X) > 2
Then
IndDone(X) = -1
'Test to see if ttt expired. If ttt not expired, load "1e9" into first
'variable then moves to next instruction. If ttt expired, issue
'aDv! command(s).
If
((Temp_Tmp(X) = 2e9)
OR
(Temp_Tmp(X) = 1e9))
Then
cmd(X) = "C"
'Start sending "C" command.
ElseIf
(Temp_Tmp(X) = NAN) Then
'Comms failed or sensor not attached
cmd(X) = "C!"
'Start measurement over