Campbell Scientific CR1000 Measurement and Control System User Manual
Page 547

Appendix B. Status Table and Settings
547
Table 122. CR1000 Settings
Settings are accessed through the Campbell Scientific Device Configuration Utility (DevConfig) via direct-serial and IP connections, or through
PakBusGraph via most CR1000 supported telecommunications options.
Setting Description
Default
Entry
Telnet Enabled
Set to 1 if the Telnet service should be enabled. This service is disabled by default.
1
Transport Layer Security (TLS)
Enabled
Specifies the password that is used to decrypt the private key file.
0
Reserved
Reserved.
0
TLS Certificate File Name
Specifies the file name for the x509 certificate in PEM format.
TLS Private Key File Name
Specifies the file name for the private key in RSA format.
TLS Private Key Password
Specifies the password that is used to decrypt the private key file.
IP Trace COM Port
This setting specifies whether, and on what port TCP/IP trace information is sent. The
type of information that is sent is controlled by the IP Trace Code setting.
Inactive
IP Trace Code
This setting controls what type of information is sent on the port specified by IP Trace
Port and via Telnet. Useful values are:
0
Trace is inactive
1
Startup and watchdog only
2 Verbose
PPP
4
Print general informational messages
16
Display net-interface error messages
256
Transport protocol (UDP/TCP/RVD) trace
8192 FTP
trace
65535 Trace
everything
0
TCP/IP Info
Currently DHCP assigned addresses, Domain Name Servers, etc.
MAC:
00d02c042ccb
eth IP:
192.168.1.99
eth mask:
255.255.240.0
eth gw:
192.168.2.19
dns svr1:
192.168.2.25
dns svr2:
192.168.2.16