Appendix B. Status Table and Settings

534 

 

 

Table 121. Status-Table Fields and Descriptions

Fieldname Description

Variable

Type

Default

Range

Edit?

Info

Type

MaxSlowProcTime9,13

The maximum time (μs)
required to process
SlowSequence scan(s).

Integer array

Status

PortStatus

Array of Boolean values
posting the state of control
ports. Values updated every
500 ms.

Boolean array of 8

False

True or False

Yes

Status

PortConfig

Array of strings explaining
the use of the associated
control port. Valid entries
are: Input, Output, SDM,
SDI-12, Tx, and Rx.

String array of 8

Input

Input or Output

Status

SW12Volts

Status of switched, 12-Vdc
port

Boolean False

True

or

False

Yes

Status

Security14

Array of the three security
settings or codes. Will not be
shown if security is enabled.

Integer array of 3

0, 0, 0

0 - 65535 (0 is
no security)

Yes Status

RS232Power

Controls whether the RS-232
port will remain active even
when communication is not
taking place. If RS-232
handshaking is enabled
(handshaking buffer size is
non-zero), this setting must
be set to yes

Boolean

0

0 or 1

RS232Handshaking

RS-232 hardware-
handshaking buffer size. If
non-zero, hardware
handshaking is active on the
RS-232 port. This setting
specifies the maximum
packet size sent between
checking for CTS.

Integer 0

RS232Timeout

RS-232 hardware-
handshaking timeout. For
RS-232 hardware
handshaking, this specifies in
tens of ms the timeout that
the datalogger will wait
between packets if CTS is
not asserted.

Integer 0