2 filecontrol command – Campbell Scientific CR1000 Measurement and Control System User Manual
Page 392

Section 8. Operation
392
*Done waiting for 100-continue
* Connection #0 to host 192.168.7.126 left intact
* Closing connection #0
When a file with extension .OBJ is uploaded to the CR1000 CPU: drive, the
CR1000 sees the file as a new operating system (OS) and does not actually upload
it to CPU:. Rather, it captures it. When capture is complete, the CR1000 reboots
and compiles the new OS in the same manner as if it was sent via a datalogger
support software
(p. 77)
Connect screen.
Other files sent to a CR1000 drive work just as they would in datalogger support
software
(p. 77)
File Control. The exception is that CRBasic program run settings
cannot be set. To get a program file to run, use the web API FileControl
command. Curl.exe can be used to perform both operations, as the following
demonstrates:
Upload the program to the CR1000 CPU: drive (must have /cpu/ on end of the
URL):
curl -XPUT -v -S -T "program.CR1" --user username:password
"http://192.168.24.106/cpu/"
Compile and run the program and mark it as the program to be run on power up. -
XGET is not needed as it is the default command for Curl.exe.
curl -v -S --user username:password
"http://192.168.24.106/?command=FileControl&file=CPU:program.CR1
&action=1"
Both operations can be combined in a batch file.
8.6.3.7.2 FileControl Command
FileControl allows a web client to perform file system operations on a host
CR1000. FileControl takes the form:
http://ip_address/?command=FileControl&file=drive:filename.dat&a
ction=x
FileControl requires a minimum .csipasswd access level of 1 (all access
allowed).