beautypg.com

Digital input/output function, Global function, Digital io as input – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 96: Digital io as output

background image

Watlow EZ-ZONE

®

RML Module

93

Chapter 6 Features

Digital Input/Output Function

Note:

Input Value is passed to either profile event inputs or ac-
tion function blocks.

Out

put Value determined by Source A and Digital Out-

put Function.

Output Function

Output Function Instance

Source Zone A

Output Low P

ower Scale

Output

Time Base

Output Control

Output High P

ower Scale

Direction

[`S2;A]

Source Zone A : 0 to 16

[`do;S]

Output State : On, Off

[`o;Ct]

Output Control : Fixed Time Base, Variable Time Base

[`o;Lo]

Output Low Power Scale : 0.0 to 100.0 %

[`o;hi]

Output High Power Scale : 0.0 to 100.0 %

[`o;tb]

Output Time Base : 0.1 to 60.0 seconds

[``Fi]

Output Function Instance : 1 to 250

[`di;S]

Input State : On, Off

Output State

Digital I/O Value

Error

[`dio]

Digital I/O Menu

[`SEt]

Operation Page

[`dio]

Digital I/O Menu

[`SEt]

Setup Page

Digital IO

Overview

Instances - 0 or 7 per RML

[`dir]

Direction : Output, Input Voltage, Input Dry Contact

[``fn]

Output Function : Off, Analog Input, Alarm, Cool Power, Heat

Power,

Compare, Counter, Digital I/O, Profile Event Out A to H,

Function Key, Logic, Linearization, Math, Process Value, Special

Function Output 1 to 4, Timer, Variable

Digital Input Value : On, Off
An error, when read, can indicate any of the following:

None, Open, Shorted, Measurement Error, Bad Cal Data,

Ambient Error, RTD Error, Fail, Math Error, Not Sourced,

Stale

Digital IO as

Input

Input State

Digital I/O Value

Error

Digital Input Value

Output Low P

ower Scale

Output

Time Base

Output Control

Output High P

ower Scale

Direction

Output Function

Output Function Instance

Source Zone A

Output Low P

ower Scale

Output

Time Base

Output Control

Output High P

ower Scale

Direction

Output State

Digital I/O Value

Error

Digital IO as

Output

Global Function

Global

Overview

Instances - 1 per RML

[AC;Lf]

AC Line Frequency : 50 Hz, 60 Hz

[d;PrS]

Display Pairs : 1 to 10

[USr;S]

User Settings Save : None, User Set 1, User Set 2*

[USr;r]

User Settings Restore : None, User Set 1, User Set 2, Factory

[C_F]

Display Units : F, C

AC Line F

requency

User Settings Restore

Displa

y Units

User Settings Sa

ve

Displa

y Plairs

[gLbL]

Global Menu

[`SEt]

Setup Page

Output Value