Digital input/output function, Global function, Digital io as input – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 96: Digital io as output
Watlow EZ-ZONE
®
RML Module
•
93
•
Chapter 6 Features
Digital Input/Output Function
Note:
Input Value is passed to either profile event inputs or ac-
tion function blocks.
Out
put Value determined by Source A and Digital Out-
put Function.
Output Function
Output Function Instance
Source Zone A
Output Low P
ower Scale
Output
Time Base
Output Control
Output High P
ower Scale
Direction
[`S2;A]
Source Zone A : 0 to 16
[`do;S]
Output State : On, Off
[`o;Ct]
Output Control : Fixed Time Base, Variable Time Base
[`o;Lo]
Output Low Power Scale : 0.0 to 100.0 %
[`o;hi]
Output High Power Scale : 0.0 to 100.0 %
[`o;tb]
Output Time Base : 0.1 to 60.0 seconds
[``Fi]
Output Function Instance : 1 to 250
[`di;S]
Input State : On, Off
Output State
Digital I/O Value
Error
[`dio]
Digital I/O Menu
[`SEt]
Operation Page
[`dio]
Digital I/O Menu
[`SEt]
Setup Page
Digital IO
Overview
Instances - 0 or 7 per RML
[`dir]
Direction : Output, Input Voltage, Input Dry Contact
[``fn]
Output Function : Off, Analog Input, Alarm, Cool Power, Heat
Power,
Compare, Counter, Digital I/O, Profile Event Out A to H,
Function Key, Logic, Linearization, Math, Process Value, Special
Function Output 1 to 4, Timer, Variable
Digital Input Value : On, Off
An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal Data,
Ambient Error, RTD Error, Fail, Math Error, Not Sourced,
Stale
Digital IO as
Input
Input State
Digital I/O Value
Error
Digital Input Value
Output Low P
ower Scale
Output
Time Base
Output Control
Output High P
ower Scale
Direction
Output Function
Output Function Instance
Source Zone A
Output Low P
ower Scale
Output
Time Base
Output Control
Output High P
ower Scale
Direction
Output State
Digital I/O Value
Error
Digital IO as
Output
Global Function
Global
Overview
Instances - 1 per RML
[AC;Lf]
AC Line Frequency : 50 Hz, 60 Hz
[d;PrS]
Display Pairs : 1 to 10
[USr;S]
User Settings Save : None, User Set 1, User Set 2*
[USr;r]
User Settings Restore : None, User Set 1, User Set 2, Factory
[C_F]
Display Units : F, C
AC Line F
requency
User Settings Restore
Displa
y Units
User Settings Sa
ve
Displa
y Plairs
[gLbL]
Global Menu
[`SEt]
Setup Page
Output Value
* Starting with firmware release 6, there is only one User Set.