Chapter 4: setup pages, Navigating the setup page – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 44
Watlow EZ-ZONE
®
RML Module
•
41
•
Chapter 4 Setup Page
Chapter 4: Setup Pages
4
[``Ai]
[`Set]
Analog Input Menu
[```1]
to [``12]
[``Ai]
Analog Input
[`SEn] Sensor Type
[`Lin] Linearization
[Unit] Units
[`S;Lo] Scale Low
[`S;hi] Scale High
[`r;Lo] Range Low
[`r;hi] Range High
[`P;EE] Process Error Enable
[`P;EL] Process Error Low
[``t;C] Thermistor Curve
[``r;r] Resistance Range
[`FiL] Filter
[`i;er] Error Latching
[`dEC] Display Precisiom
[`i;Ca] Calibration Offset
[`Ain] Process Value
[`i;Er] Error Status
[`dio]
[`Set]
Digital Input/Output Menu
[```1]
to [```6] and [```9]
[`dio]
Digital Input/Output 1 (to 12)
[`dir]
Direction
[``Fn]
Function
[``Fi]
Function Instance
[`S2;A]
Source Zone A
[`o;Ct]
Control
[`o;tb]
Time Base
[`o;Lo]
Low Power Scale
[`o;hi]
High Power Scale
[`ACt]
[`Set]
Action Menu
[```1]
to [``16]
[`ACt]
Action
[``Fn]
Function
[``Fi]
Function Instance
[SFn;A] Source Function A
[`Si;A]
Source Instance A
[`S2;A]
Source Zone A
[`LEu]
Active Level
[LiM]
[`Set]
Limit Menu
[```1]
to [``12]
[LiM]
Limit
[`L;SD]
Sides
[`L;hy] Hysteresis
[SP;Lh]
Set Point Limit High
[SP;LL]
Set Point Limit Low
[`Lh;S] High Set Point
[`LL;S] Low Set Point
[SFn;A] Source Function A
[`Si;A]
Source Instance A
[`S2;A]
Source Zone A
[`l;Cr] Clear Request
[`l;st] Status
[otpt]
[`Set]
Output Menu
[```1]
to [``10], [```7] to [``10
[otpt]
Output
[``Fn]
Function
[``Fi]
Function Instance
[`S2;A]
Source Zone A
[`o;Ct]
Control
[`o;tb]
Time Base
[`o;Lo]
Low Power Scale
[`o;hi]
High Power Scale
[ALM]
[`Set]
Alarm Menu
[```1]
to [``16]
[ALM]
Alarm
[`A;ty]
Type
[SFn;A] Source Function A
[`Si;A]
Source Instance A
[`S2;A]
Source Zone A
[`A;hy]
Hysteresis
[`a;Lg]
Logic
[`A;SD]
Sides
[`A;Lo] Low Set Point
[`A;hi]
High Set Point
[`a;LA]
Latching
[`A;bL]
Blocking
[`a;Si]
Silencing
[A;dsp]
Display
[`A;dL]
Delay
[a;Clr] Clear Request
[a;sir] Silence Request
[`A;st] State
Navigating the Setup Page
Note:
Some of these menus and parameters may not appear, depending on the controller's options. See model
number information in the Appendix for more information. If there is only one instance of a menu, no sub-
menus will appear.
Note:
Some of the listed parameters may not be visible. Parameter visibility is dependent upon controller part
number.
To navigate to the Setup Page using the RUI, follow
the steps below:
1. From the Home Page, press and hold both the Up ¿
and Down ¯ keys for six seconds. [``Ai] will ap-
pear in the upper display and [`Set] will appear in
the lower display.
Note:
If keys are released when [OPEr] is displayed,
press the Infinity Key ˆ or reset key to exit and
repeat until [`Set] is displayed.
2. Press the Up ¿ or Down ¯ key to view available
menus.
3. Press the Advance Key
‰
to enter the menu of
choice.
4. If a submenu exists (more than one instance), press
the Up ¿ or Down ¯ key to select and then press
the Advance Key
‰
to enter.
5. Press the Up ¿ or Down ¯ key to move through
available menu prompts.
6. Press the Infinity Key ˆ to move backwards
through the levels: parameter to submenu; submenu
to menu; menu to Home Page.
7. Press and hold the Infinity Key ˆ for two seconds to
return to the Home Page.
On the following pages, top level menus are identified